Alarm, Alarm -10, Oxybalance oxygen display and averaging system – Emerson OXYBALANCE IM-106-4050 User Manual

Page 26

Advertising
background image

3-10

Instruction Manual

IM-106-4050 Original Issue

March 2006

OxyBalance Oxygen Display
and Averaging System

Alarm

There are two divisions of the Alarm tab: Active Alarms and Alarm History,
shown in Figure 3-9 and Figure 3-10.

There are four possible reports that can be displayed.

Average # 1-4 warning

This appears when one of the probes fails or is in calibration. When this Alarm
appears, the average channel will still display an average O

2

% for the

remaining probes in the group.

Average # 1-4 failed

This appears when less than 2 probes in the group are transmitting data for
the average calculation. No average percentage will be calculated.

Probe # 1-8 calibration in progress

This means that the probe is calibrating and will automatically join its specified
group when the calibration is complete. Probes in calibration are not factored
into the channel average.

Probe #1-8 failed

This means the probe has failed and needs to be checked. Refer to Section 6,
Troubleshooting.