Operating Inverter is quite easy. During normal operation, Inverter runs

automatically. However, to achieve maximum conversion efficiency of

Inverter, please read through the following information:

1.

Automatic ON-OFF: Inverter starts up automatically when DC-power

from the PV panel is sufficient. Once the PV-Inverter starts it enters

one of the following 3 states:

z

Standby: The PV string can only provide just enough voltage to

minimum requirements of the controller.

z

Waiting: When the PV string DC voltage is greater than 100V,

Inverter enters a “waiting” state and attempts to connect to the

grid.

z

Normal operation: When PV string DC voltage is greater than

150V, Inverter operates in the normal state.

In this state, it feeds power to the grid.

Inverter automatically stops when the PV power is

not enough.

2.

Starting-up display sequence: Once the PV power

is sufficient, Inverter displays information as

shown in the flow chart to the right.

3. Change display information: During normal

operation, LCD shows the detail of PV-Inverter.

On the other hand, the display is setup to

automatically indicate the supplying power to the

grid. Each subsequent press changes the display

by press the “Function” key on the front panel.

Model

Waiting

Checking= xxxS

Normal State

Pac =xxxx.xW

Information during

start-up

4.

Hold display: If you want to hold a specific display.

Edition 1.6E, 2010/06

20