8. Trouble shooting

In most situations, the Inverter requires very little service. However, if

Inverter is not able to work perfectly, please refer to the following instructions

before calling your local dealer.

z

Should any problems arise, the red (Fault) LED on the front panel turns

on and the LCD displays the relevant information. Please refer to the

following table for a list of potential problems and their solutions.

Display

Possible actions

Isolation Fault

1. Check the impedance is between PV (+) & PV

(-) and the PV-Inverter is earthed. The
impedance must be greater than 5M

Ω

2. If the problem persists please contact Eaton.

Ground I Fault

1. The ground current is too high.
2. Unplug the inputs from the PV generator and

check the peripheral AC system

3. After the cause is cleared, re-plug the PV panel

and check PV-Inverter status.

4. If the problem persists please contact Eaton.

Grid Fault

1. Wait for 5 minutes, if the grid returns to normal,

PV-Inverter automatically restarts.

2. Make sure grid voltage and frequency meet the

specifications

3. If the problem persists please contact Eaton.

System
Fault

No Utility

1. Grid is not connected.
2. Check grid connection cables.
3. Check grid usability.

PV over

Voltage

1. Check the open PV voltage, see if it is greater

than or too close to 450VDC

2. If PV voltage is less than 450VDC, and the

problem still occurs, please contact Eaton.

Inverter
Failure

Consistent

Fault

1. Disconnect PV (+) or PV (-) from the input,

restart the PV-Inverter

2. If it does not work, please Contact Eaton.