Liebert iCOM Display Components and Functions

9

Figure 3

Liebert iCOM default screen symbols

4.1

Navigating Through the Liebert iCOM Display

Liebert iCOM displays icons and text for monitoring and controlling your Liebert cooling unit. The

number of icons and amount of text shown depends on the display size.
The Liebert iCOM offers two different types of views: graphical and simple. The graphical view is the

default; to set the simple view refer to 4.3 - Changing Liebert iCOM’s Display Settings. The Lie-

bert iCOM’s home screen is shown in Figure 4 (graphical view) and in Figure 5 (simple view).

Figure 4

Liebert iCOM default home screen—Graphical view

fan

cooling

maintenance

hot water

electric heat

dehumidification

humidification

freecooling

7/29/2009 08 :28 (01) MSG UNIT ON
7/29/2009 08 :27 (01) MSG POWER ON

UNIT 1

7/29/2009 09 :18:07

50

72.0°F

50%

51.6

°F

%

SET

ACT

UNIT ON

for nex t / pr ev uni t for s y s tem v i ew
for menu for previous screen ? for help

E S C

73.6

°F

100%

60%

FC

0%

03/2010

0%

0%

0%

0%

System or

Unit # view

Temperature

Sensor Reading

Evaporator

Fan Speed

Percent

Cooling

Free-Cooling

Percentage

Next

Maintenance

Date and

Time

Temperature

Setpoint

Return Air

Humidity

Setpoint

Humidity Sensor

Reading

Supply Air (requires

optional supply air

sensor)

Supply

Air Temperature

Percent

Electric

Heating

Percent

Dehumidifying

System

(or Unit)

On/Off

Most recent Mes-

sage (MSG), Alarm

(ALM) or Warning

(WRN) with Date,

Time, Unit and

Description)

Percent

Hot Water

Heating