2 accessing menus and settings, Viewing data, 3 entering the password – Emerson Liebert Challenger With Liebert iCOM Control 3000/ITR User Manual

Page 17: Figure 6 entering the password, Accessing menus and settings, Entering the password, Figure 6

Advertising
background image

Liebert iCOM Display Components and Functions

11

4.1.2 Accessing Menus and Settings

Viewing Data

No password is required to view data or settings.
To view data:
1. From the home screen, press the Enter key to view the User Menu (see Figure 8).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the icon for the data you wish to view.
4. Once that icon is highlighted, press Enter again to open that menu.

• If a password is required, see 4.1.3 - Entering the Password.
• If a menu has more than one screen, the Liebert iCOM display will have text at the top simi-

lar to this: (page 1 of 2).

5. Press Enter to select the first line of data.
6. Use the Up and Down arrow keys to scroll to the desired data point.
7. Press ESC to move back to higher level menus.

4.1.3 Entering the Password

Most settings in the Liebert iCOM are protected by a factory-set password, 1490. To enter the pass-

word:
1. From the home screen, press the Enter key to view the User Menu (see Figure 8).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the icon for the data you wish to change.
4. Once that icon is highlighted, press Enter again to open that menu.
5. Press Enter to highlight the Password line.
6. With the Password line highlighted, press Enter to highlight the first digit in the password
7. Enter the password, 1490.

Use the Up and Down arrow keys to select a numeral for the first digit of the password.
Move to the next digit of the password with the Right arrow key.
Select the numerals for all four digits with the same process.

8. After all four digits of the password have been entered, press the Enter key.

Figure 6

Entering the password

NOTE
Do not press the ESC key or the Liebert iCOM will move to the previous screen and the

password must be re-entered before changes may be made.

SETPOINTS

for nex t /pr ev uni t to s el ec t par ameter
then to change parameter to confirm

UNIT 01

PASSWORD (Actual Level 3)
Temperature Setpoint
Humidity Setpoint
Humidity Control Type
Supply Sensor
Supply Setpoint
Backup Temperature Setpoint

U101
U102
U103
U104
U105
U106
U107
U108
U109
U110
U111

????

72°F

50.0%

Relative

Disabled

°F

73°F

Password command line—highlight

by pressing Enter

After highlighting the Password command line, press

Enter again to highlight the first digit. Use the Up and

Down arrow keys to change the first digit. Move to the

next digit in the Password with the right arrow.

Password is

factory-set

at 1490