Figure 2 low volt wiring terminals, Liebert thermostat, Dual unit control – Emerson 2 User Manual

Page 13: Tele2, Figure 2, Low volt wiring terminals, Warning

Advertising
background image

Installation

7

Figure 2

Low volt wiring terminals

Liebert Thermostat

See 2.5.2 - Control Connections for further information, refer to the detailed instructions that ship

with the thermostat.

Dual Unit Control

The InteleCool

®

Dual Unit Control is designed to control two InteleCools in a “lead/lag” fashion. The

control contains an electronic timer for switching the operating sequence of two units on a one-, two-,

four-, or eight-day basis. It also contains a two-stage heat/two-stage cool thermostat with individual

heat and cool set points. Light emitting diodes (LEDs) indicate Lead Unit 1 or 2 and power from

Unit 1 or 2. The schedule for lead/lag switchover is adjustable by moving jumpers on the printed cir-

cuit board. A jumper is also used to change lead and lag unit before a scheduled changeover (if neces-

sary for servicing).

Tele2

Consult the Tele2 user manual for installation instructions.

NOTE
This control contains mercury in a sealed tube. Do not place control in the trash at the end of is

useful life. If this control is replacing a control that contains mercury in a sealed tube, do not

place your old control in the trash. Contact your local waste management authority for

instructions regarding recycling and the proper disposal of this control, or of an old control

containing mercury in a sealed tube.

If you have questions, call the thermostat manufacturer, Honeywell, at 800-468-1502.

!

WARNING

The original Dual Unit Control (part # 153054G1, produced through March 2002), is phase

sensitive. The latest version Dual Unit Control (Part # 171170G1) is not. Please refer to

specific installation instructions supplied with each control. Failure to follow specific

instructions may damage the control and/or the unit and void the warranty.

NOTE
This control contains mercury in a sealed tube. Do not place control in the trash at the end of

its useful life. If this control is replacing a control that contains mercury in a sealed tube, do

not place your old control in the trash. Contact your local waste management authority for

instructions regarding recycling and the proper disposal of this control, or of an old control

containing mercury in a sealed tube.

If you have questions, call the thermostat manufacturer, Honeywell, at 800-468-1502.