Troubleshooting

27

8.0

T

ROUBLESHOOTING

Table 14

Troubleshooting guide

Problem

Probable Cause

Remedy

Unit will not start

No power to unit

Check voltage to input circuit breaker.

Control voltage circuit

breaker open

Locate short and reset breaker.

Shut off by external

thermostat or stat is

defective

Check operation of thermostat.

No cooling

Low refrigerant

charge

Check with gauges.

Compressor contactor

not pulling in

Check voltage at contactor. If not present refer to print and determine

voltage loss. Check enthalpy sensor for full CCW or D setting.

No output from

thermostat

Check operation of stat. Should have voltage output to Y terminal during

cooling.

Unit cycles on

high pressure switch

Loss or restriction of

air flow

Check condenser blower assembly for proper operation. Check for dirty

coil or inlet grille restriction.

Defective fan cycling

control

Switch should make @ 240 PSIG

±10 (1655 kPa ±68.9). (Check settings

on adjustable switch when supplied.)

Heat does not operate

No voltage output

from thermostat

Check stat for proper output to W terminal.

Fuseable link blown

Check for open and replace.

Bad contactor

Check for open and replace.