Operation

11

5.0

O

PERATION

5.1

Compressorized Cooling

Compressorized cooling is provided by a high efficiency system consisting of a compressor, thermo-

static expansion valve, evaporator, and condenser coil.
The InteleCool2 uses R-22 refrigerant in a conventional vapor-compression refrigeration cycle. Heat

is removed from the air in the space by blowing the air across the evaporator coil. As heat is trans-

ferred to the refrigerant in the evaporator, the refrigerant boils and turns to a warm vapor. The

refrigerant vapor enters the compressor and is compressed, resulting in high pressure and tempera-

ture. After entering the condenser, the hot vapor is condensed to a liquid by the air blown across the

condenser coil. Liquid refrigerant then passes through the thermal expansion valve and into the evap-

orator. The expansion reduces the pressure and temperature to complete the cycle.

Figure 4

Refrigeration system

Condenser

Compressors:

Hermetic Reciprocating (1.5, 2 and 3 ton units)

or Scroll

Optional compressor location available

Evaporator

Liquid line

Filter drier

Liquid line

Thermal expansion

valve (not shown)