UPS configurations

1. Various settings that have been chosen are shown in the UPS setting display.

2. To enter configuration mode, press the “FUNC” button for one second. The first

configuration parameter will be shown on the LCD display.

3. Press the “FUNC” button to scroll through the parameters.

4. Press the “ENTER” button to select the parameter.

5. Press the “FUNC” button to scroll through the options for the selected parameter.

6. Press the “ENTER” button to select the option.

You may be prompted to save the selection, if so press the “ENTER” button to either
confirm or save your selection. Other options are saved and started automatically. See
the table below for further details.

7. If no buttons are pressed (or user inactivity) for ten seconds, the UPS shall exit the

configuration mode and return to normal mode displaying Line mode.

Caution!

The factory default settings do not necessarily have to be changed, although you are free to
tailor the UPS to your specific needs.

23

Settings

LCD
display

Explanation Selection

Factory
default

Output Volt.Setting

O/P V
Setting

Select Nominal Voltage

208/220/230/240 V

230V

Input/Frequency I/P

F

Setting

Select input frequency
range when UPS goes into
free run mode

±2%
±5%
±7%

±5%

Input/Bypass
Voltage

I/P Bypass
Set

Select Input Voltage range
when bypass is available

±10%
+10/-15%
+15/-20%

+10/-15%

Free Run Mode

Free Run
Set

Select if UPS can run in
Free run mode
(unsynchronized)

ON/OFF ON

Bypass
Enable/Disable at
Free run mode

Bypass
disable

If Enable is chosen, the
UPS can go to bypass when
unsynchronized.

Disable/Enable Disable

He mode Setting

HE Mode
Set

Select if UPS runs in high
efficiency mode

ON/OFF OFF

Force Manual
Bypass

Manual
bypass

Permanently force UPS to
bypass. For service only.**

ON/OFF

OFF

Do Battery Test

Battery Test

Detect battery is normal or
not.

Silence Function

Silence Set

Enable or disable silence
function

ON/OFF

OFF

Number of
External battery
Packs

Bat Cabinet
Set

This setting is needed
For UPS to predict
Backup time

0 (only internal batteries)
1(one external cabinet)
2 (two external cabinets)

0

Site wiring alarm

Sit Fault Set

You can enable or disable
the site wiring alarm

Enable /Disable

Disable

Select Language

Language

Select load language

English, German, French,
Spanish, Italian.

English

Set Generator Mode Generator

Set unit in generator mode.
***

ON/OFF OFF

Set RS232
communication

RS232
Control

Set RS232 communication
enable or disable

Enable/Disable Enable

Manual test of the UPS

Manual UPS or Manual Battery tests can be conducted from the UPS configuration as well
and are functional even when the UPS is not charging the battery.

Manual Battery test: Scroll the parameters until Manual Bat test displays on the LCD.

Press the “ENTER” button twice.