7.5 Trouble shooting

Displayed on LCD

Audible Alarm Alarm Description

What You Should Do

Output Overload

Two Beeps per
second

The UPS is overloaded (in
Line Mode). Your
equipment needs more
power than the UPS can
provide. The UPS operates
in bypass.

Shut off the least important
equipment connected to the
UPS. If this solves the
overload problem, the UPS
will switch from bypass back
to normal operation.

Battery Test

No Beeps

The UPS is doing a battery

test.

No action needed. The UPS

will return to normal operation

when it successfully completes

the battery test.

Over-Charge Constant

beep

Batteries are
overcharged.

Turn off protected loads. Turn
off UPS and call your local
dealer

Low Battery

2 beeps every
5seconds

The unit is operating on
Battery Power and will shut
down soon due to very low
battery voltage

The unit will restart
Automatically when
acceptable power returns.

On-Battery

Once every 5
seconds

The unit is operating on
Battery Power.

Save your data and perform a
controlled shutdown.

Charger Failure

Constant beep

Charger has failed.

Phone the local dealer

Over-Temperature

Constant beep

High ambient Temperature.

Make sure the unit’s fans and
vent holes are not blocked, and
make sure the ambient
surrounding temperature is not
above 40 degree C. If these
conditions did not solve the
problem, call your service
representative.

Output Short

Constant beep

Output short circuit

Call the Local dealer

High output Voltage

Constant beep

High output voltage

Call the Local dealer

Low Output Voltage

Constant beep

Low output voltage

Call the Local dealer

Bus Fault

2 Beeps per
second

High internal DC bus
Voltage.

Turn off protected loads. Turn
off UPS and call your local
dealer

Site wiring Fault

1 Beep per
second

Voltage detected Between
Neutral and Ground

UPS mains connector polarity
Wrong. Rotate the connector
(Schuko). UPS installed to
mains supply without ground.
See page 15 on how to disable
the Site wiring alarm

Line abnormal

1 Beep per
second

Wrong AC Line backed up
during auto restart

27

8. Maintenance

With a minimal amount of maintenance, you can expect the UPS to application, otherwise
consider changing the batteries. have a long life free of trouble. The most critical issues for
the reliability of the UPS are environmental issues. Ensure that the temperature and humidity
are always according to specifications and keep the area around the unit clean and dust free.

At a temperature of 25°C, the typical battery lifetime is 4 years.

Also check at regular intervals of 6 to 12 months whether the back-up time of the battery is
adequate for its

WARNING!

Batteries may cause electrical shock or burn from high short circuit

currents. Please observe the following precautions: 1. Remove jewelry and metal
objects such as watches and rings. 2. Use tools that have insulated handles. 3. Keep
tools and other metal objects from contacting and away from the batteries.

ELECTRIC ENERGY HAZARD. Do not attempt to rewire, alter, or change any
battery wiring or connectors. Attempting to make such alterations can cause
injury.

Replace the batteries with the same number and type as originally installed
batteries.

DO NOT DISCONNECT the batteries while UPS is in Battery mode.