Enerco HSVFR10LPT User Manual

Page 5

Advertising
background image

5

Installation Instructions and Owner’s Manual

Unvented Liquid Propane Fired Room Heater

attics* and crawl spaces. Follow the National Fuel Gas

Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for Com-

bustion and Ventilation for required size of ventilation

grills or ducts.

*IMPORTANT: Do not provide openings for inlet or

outlet into attic. If attic has a thermostat-controlled

power vent, heated air entering the attic will activate

the power vent.
IMPORTANT: Vent-free heaters add moisture to

the air. Although this is beneficial, installing heater

in rooms without enough ventilation air may cause

mildew to form from too much moisture. See Fresh

Air for Combustion and Ventilation, pages 3

through 5.

INSTALLATION

NOTICE: This heater is intended for the use as supple-

mental heat. Use this heater along with your primary

heating system. Do not install this heater as your pri-

mary heat source. If you have a central heating system,

you may run system’s circulating blower while using

heater. This will help circulate the heat throughout the

house. In the event of a power outage, you can use this

heater as your primary heat source for the duration of

the outage.

heater, Gas furnace, Vented gas heater, Gas fire-

place logs, and Other gas appliances*

*Do not include direct-vent gas appliances. Direct-

vent draws combustion air from the outdoors and

vents to the outdoors.
Example:
Gas water heater 40,000 Btu/hr
Vent Free Heater + 20,000 Btu/hr
Total

=60,000 Btu/hr

4. Compare the maximum Btu/hr the space can support

with the actual amount of Btu/hr used.
Example: 51,800 Btu/hr (maximum Btu/hr the

space can support)

60,000 Btu/hr (Actual amount of Btu/hr used)

The space in the above example is a confined

space because the actual Btu/hr used is more than

the maximum Btu/hr the space can support.

You must provide additional fresh air. Your options

are as follows:
A. Rework worksheet, and the space of an adjoining

room. If the extra space provides an unconfined

space, remove door to adjoining room or add venti-

lation grills between the rooms. See Ventilation Air

From Inside Building (Fig. 2)

B. Vent room directly to the outdoors. See Ventilation

Air From Outdoors (Fig. 3).

C. Install a lower Btu/hr heater if lower Btu/hr size

makes room unconfined.

If actual Btu/hr used is less than the maximum Btu/

hr the space can support, the space is an uncon-

fined space. You will need no additional fresh air

ventilation.

VENTILATION AIR
Ventilation from Inside Building

This fresh air would come from an adjoining unconfined

space. When ventilation to an adjoining unconfined

space, you must provide two permanent openings: one

within 12” of the ceiling and one within 12” of the floor

on the wall connecting the two spaces (see options 1

& 2 of figure 2). You can also remove door into adjoin-

ing room (see option3, fig 2). Follow the National Fuel

Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for

Combustion and Ventilation for required size of ventila-

tion grills or ducts.

WARNING: Rework worksheet, adding the space

of the adjoining unconfined space. The combined

space must have enough fresh air to supply all ap-

pliance in both spaces.

Ventilation from Outdoors

If necessary provide extra fresh air by using ventila-

tion grills or ducts. Connect these items directly to the

outdoors or spaces open to the outdoors. These include

Ventilation

Gills into

Adjoining

Room - Op-

tion 1

Ventilation Gills into Ad-

joining Room - Option 2

12”

12”

Or remove

door into

Adjoining

Room -

Option 3

INLET

AIR

OUTLET

AIR

VENTILATION CRAWL SPACE

TO CRAWL

SPACE

TO ATTIC

VENTILATION AIR

VENTILATED

ATTIC

OUTLET AIR

Figure 2

Figure 3.

Advertising
This manual is related to the following products: