Pilot flame characteristics thermostat operation – Empire Comfort Systems SR-10T-3 User Manual

Page 14

Advertising
background image

16941-5-0907

Page 14

The correct flame will be blue and will extend beyond the ther-

mocouple. The flame will surround the thermocouple just below

the tip. A slight yellow flame may occur where the pilot flame and

main burner flame meet.

Figure 13

Oxygen Depletion Sensor Pilot (Figure 14)

When the pilot has a large yellow tip flame, clean the Oxygen

Depletion Sensor as follows:
1. Clean the ODS pilot by loosening nut B from the pilot tubing.

When this procedure is required, grasp nut A with an open end

wrench.

2. Blow air pressure through the holes indicated by the arrows.

This will blow our foreign materials such as dust, lint and

spider webs. Tighten nut B also by grasping nut A.

Figure 14

Never use needles, wires, or similar cylindrical objects to

clean the pilot to avoid damaging the calibrated ruby that

controls the gas flow.

To ignite main burner, turn gas control knob counterclockwise to-

ward HI setting. To shut down main burner, turn gas control knob

clockwise toward LO setting.
The SR-10T has an input of 10,000 BTUH (2.9KW/H). The hy-

draulic thermostat bulb is located at the casing assembly bottom.

When the hydraulic thermostat bulb senses the need for heat, the

unit cycles “ON” at a full input rate of 10,000 BTUH (2.9KW/H).

The unit remains at this full input rate until the hydraulic thermostat

bulb is “satisfied.” When the hydraulic thermostat bulb is “satisfied”

the burner will shut “OFF” with the pilot flame remaining “ON.”
The SR-18T has an input of 18,000 BTUH (5.3KW/H). The hy-

draulic thermostat bulb is located at the casing assembly bottom.

When the hydraulic thermostat bulb senses the need for heat, the

unit cycles “ON” at a full input rate of 18,000 BTUH (5.3KW/H).

The unit remains at this full input rate until the hydraulic thermostat

bulb is “satisfied.” When the hydraulic thermostat bulb is “satisfied”

the burner will shut “OFF” with the pilot flame remaining “ON.”
Note: The burner does not modulate between “ON” and the pilot

flame. When the SR-18T is “ON,” all three ceramic plaques will

“glow.” There will never be a time when only one or two ceramic

plaques are “glowing.”
The SR-30T has an input of 30,000 BTUH (8.8KW/H). The hy-

draulic thermostat bulb is located at the casing assembly bottom.

When the hydraulic thermostat bulb senses the need for heat, the

unit cycles “ON” at a full input rate of 30,000 BTUH (8.8KW/H).

The unit remains at this full input rate until the hydraulic thermostat

bulb is “satisfied.” When the hydraulic thermostat bulb is “satisfied”

the burner will shut “OFF” with the pilot flame remaining “ON.”
Note: The burner does not modulate between “ON” and the pilot

flame. When the SR-30T is “ON,” all five ceramic plaques will

“glow.” There will never be a time when only one or three ceramic

plaques are “glowing.”
The LO and HI setting has temperature range of approximately 55°F

(12.78°C) to 90°F (32.22°C), respectively. This is the temperature at

the hydraulic thermostat bulb not the room temperature. The owner

is advised to determine the particular heat setting that is desired for

comfort, as heating requirements are different for every owner.
Attention: If the owner does not want the main burner to ignite

and turns the gas control knob to the LO setting, the main burner

will still ignite if the temperature at the hydraulic thermostat bulb

drops to 55°F (12.78°C).
If no heat is desired, turn the gas control knob to the PILOT posi-

tion.
Main Burner Operation

Description of Gas Control Knob:
OFF position.
PILOT position.
LO/HI will allow the hydraulic thermostat bulb to cycle the heater

ON and OFF.

PILOT FLAME CHARACTERISTICS

THERMOSTAT OPERATION

Advertising