XTRA Series • Installation

Installation, cont’d

2-4

XTRA Series • Installation

2-5

1

.

Elevated operating ambient temperature

— If installed

in a closed or multi-unit rack assembly, the operating

ambient temperature of the rack environment may be

greater than room ambient temperature. Therefore, install

the equipment in an environment compatible with the

maximum ambient temperature (Tma = +122 °F, +50 °C)

specified by Extron.

2

.

Reduced air flow

— Install the equipment in a rack so that

the amount of air flow required for safe operation of the

equipment is not compromised.

3

.

Mechanical loading

— Mount the equipment in the rack

so that a hazardous condition is not achieved due to

uneven mechanical loading.

4

.

Circuit overloading

— Connect the equipment to

the supply circuit and consider the effect that circuit

overloading might have on overcurrent protection and

supply wiring. Appropriate consideration of equipment

nameplate ratings should be used when addressing this

concern.

5

.

Reliable earthing (grounding)

— Maintain reliable

grounding of rack-mounted equipment. Pay particular

attention to supply connections other than direct

connections to the branch circuit (e.g. use of power strips).

Rack mounting

The XPA 1002 or XPA 2001 can be mounted in a rack shelf using

the optional RSU 129 1U Universal rack shelf (Extron part

#60-190-01

) or the 1U Basic rack shelf (Extron part #60-604-01),

as follows.
1

.

If feet were installed on the bottom of the amplifier,

remove them.

2

.

Place the amplifier on one half of the rack shelf. Align the

front of the amplifier with the front of the shelf, and align

the threaded holes on the bottom of the amplifier with the

holes in the rack shelf.

3

.

Attach the amplifier to the rack shelf with the two

provided 4-40 x 3/16” machine screws. Insert the screws

from the underside of the shelf, and securely fasten them

into diagonally-opposite corners.

See the following illustration.

Use 2 mounting holes on
opposite corners.

(2) 4-40 x 3/16"
Screws

NOTE:

Using screws longer

than 3/16” will damage the
unit and void the warranty.

1U Universal Rack Shelf

Front false
faceplate
uses 2
screws.

1/2 Rack Width Front False
Faceplate

Rack mounting of the amplifier

4

.

Attach the false front panel (provided with rack shelf part

#60-190-01

) to the unoccupied side of the rack (as shown

above), or install a second half-rack-width device in that

side by repeating steps 1 through 3.

5

.

Attach the rack shelf to the rack using four 10-32 x ¾" bolts

(provided). Insert the bolts through #10 beveled washers,

then through the holes in the rack, as shown above.

Rack mounting ventilation recommendations

Excessive heat can decrease the optimal lifetime of the power

amplifier. An over temp indicator LED on the front panel of

the amplifier lights red whenever the recommended ambient

temperature has been exceeded (see "Front Panel Features and

Operation" in chapter 3).
To reduce the chances for an over temp condition, the XPA(s)

should be arranged in a rack environment so that adequate

airflow is available both above and below the XPA whenever

possible. No more than two XPAs should be arranged one-

on-top-of-the-other in a rack without an open space between

them, as shown in the following illustration. An XPA can also

be arranged above or below another non-XPA device, but there

must be an open space both above and below those devices.