VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space.

When ventilating to an adjoining unconfined space, you must

provide two permanent openings: one within 12" of the ceiling

and one within 12" of the floor on the wall connecting the two

spaces (see options 1 and 2, Figure 5). You can also remove door

into adjoining room (see option 3, Figure 5). Each ventilation grill

or opening shall have a minimum free area of one square inch per

1,000 BTU/HR of the total input rating of the gas equipment in

the confined space.

Figure 5

WARNING: Rework worksheet, adding the space of the

adjoining unconfined space. The combined spaces must have

enough fresh air to supply all appliances in both spaces.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must

provide two permanent openings: one within 12" of the ceiling

and one with 12" of the floor. Connect these items directly to the

outdoors or spaces open to the outdoors. These spaces include

attics and crawl spaces. In most cases for direct communication

with the outdoors or direct communication through a vertical duct

a free area opening of one square inch per 4,000 BTU/HR of heater

input rating for each grill. If a horizontal duct is used, a grill free

area or duct opening shall have a free area opening of one square

inch per 2,000 BTU/HR for each grill. Follow the National Fuel

Code NFPA 54/ANSI Z223.1, Section 5.3 Air for Combustion and

Ventilation for required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet or outlet air

into attic if attic has a thermostat-controlled power vent. Heated

air entering the attic will activate the power vent.

Figure 6

PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR