Air handler coil data line set sizes, Air handler nomenclature – Envision Peripherals Series User Manual

Page 11

Advertising
background image

9

NS SPLIT INSTALLATION MANUAL

Air Handler Coil Data

Line Set Sizes

Envision

Split Model

Matching Air

Handler

Coil Surface

Area (sq ft.)

FPI

Rows

Tube

Diameter

022 - 038

042 - 072

NAH060

5.83

12

3

3/8"

NAH036

5.83

12

2

3/8"

Unit

Air

Factory

Size

Handler

Suction

Liquid

Suction

Liquid

Suction

Liquid

Charge (oz.)

NDS026

NAH026

5/8" OD

3/8" OD

3/4" OD

3/8" OD

3/4" OD

1/2" OD

52

NDS038

NAH036

5/8" OD

3/8" OD

3/4" OD

3/8" OD

3/4" OD

1/2" OD

56

NDS049

NAH048

3/4" OD

3/8" OD

7/8" OD

3/8" OD

7/8" OD

1/2" OD

90

NDS064

NAH060

7/8" OD

1/2" OD

7/8" OD

1/2" OD

1-1/8" OD

1/2" OD

92

NDS072

NAH060

7/8" OD

1/2" OD

7/8" OD

1/2" OD

1-1/8" OD

1/2" OD

104

Notes: Lineset charge for R410A is 0.50 oz. per ft. for 3/8" and 1.0 oz. per ft. for 1/2" tube.

Rev.: 4/1/08

Initial Total System Charge = Factory Split charge + lineset charge + 20 oz, then adjust charge by subcooling and superheat measurements.

20 feet

40 feet

60 feet

Air Handler Nomenclature

NAH

036

A

00

0

1

R

Model Type

Air Coil

NAH = Envision Air Handler

R = Refrigerant
H = Hydronic

Unit Capacity
Refrigerant Models

Nom. CFM

Motor

022 MBTUH

800

1 = ECM 208-230/60/1

026 MBTUH

925

030 MBTUH

980

036 MBTUH

1225

042 MBTUH

1425

Disconnect

048 MBTUH

1625

0 = No breaker installed (only on 5kW & 10 kW heaters )

060 MBTUH

1760

1 = Breaker installed (only on 15kW & 20kW heaters)

Hydronic Models

026 MBTUH

925

036 MBTUH

1225

Electric Heat

048 MBTUH

1625

00 = No electric heat

060 MBTUH

1760

05 = 5 kW (available on 022-036)
10 = 10 kW (available on 030-060)

Vintage

Note: Kit NAHBC must be ordered to field convert the NAH042-060 to bottomflow air discharge

15 = 15 kW (available on 042-060)

A = Current

20 = 20 kW (available on 060 only)