NS SPLIT INSTALLATION MANUAL

DIP Switch Settings

DIP SWITCH

NUMBER

DESCRIPTION

OFF POSITION

ON POSITION

SW1

N/A

NOT USED

N/A

N/A

SW2

1

Service/Test Mode - Allows control of “NORM” or “TEST” opera-

tional modes. Test mode accelerates most timing functions 16

times to allow faster troubleshooting. Test mode also allows view-

ing the “CURRENT” status of the fault inputs on the LED display.

Test

Norm

2

Freeze Sensing Setting
Allows field selection of freeze thermistor fault sensing tempera-

tures for well water (30°F) or antifreeze-protected (15°F) earth

loops.

Loop

(Sensing 15° F)

Well

(Sensing 30° F)

3

Accessory Relay
Allows field selection of the accessory relay to operate with the

compressor or fan.

Fan

Comp

4

NOT USED

N/A

N/A

5

NOT USED

N/A

N/A

6

Input Diagnostics - Allows viewing the inputs from the thermo-

stat to the control board such as Y1, Y2, O, G, W, SL1-In on the

LED display.

Diagnostic Inputs

viewed at LEDs

Normal Display

viewed at LEDs

7

Output Diagnostics - Allows viewing the outputs from the control

board such as the compressor, reversing valve, blower, hot water

pump, and loop pump on the LED display.

Diagnostic

Outputs viewed at

LEDs

Normal

Display viewed

at LEDs

8

Thermostat Selection

Configures the control for a pulsed lockout signal (ComforTalk and

FaultFlash thermostats) or continuous 5 VAC lockout signal.

Pulsed “L”

signal

Continuous “L”

signal

SW3

1

Single or Dual Capacity Operation

Dual Cap

1 Speed

2

Zoned/Finish on Second Stage
This switch allows the unit to down stage with the thermostat

when off and finish with second stage when on. Finish on second

stage reduces stage changing in reciprocating dual capacity

compressors.

Normal -

All other systems

Finish on 2nd

Unzoned Dual

Capacity

E-Series or

Premier 2 speed

3

ECM Fan Monitoring - Set for No PRM on split systems

No RPM

RPM

4

NOT USED

N/A

N/A

5

On dual capacity units this switch allows stage change: on the fly

when off, and 1 minute delay when on. A delay is required on all

reciprocating dual capacity units.

Envision

E-Series or

Premier