Thermostat wiring, Electrical, General – Envision Peripherals Series User Manual

Page 9

Advertising
background image

7

NS SPLIT INSTALLATION MANUAL

Rated

Voltage

HWA

Ext

Total

Min

Max

Model

Voltage

Min/Max

Pump

Loop

Unit

Circ

Fuse/

MCC

RLA

LRA

FLA

FLA

FLA

Amp

HACR

026

208-230/60/1

197/253

16.0

10.2

52.0

0.4

5.4

16.0

18.6

25

038

208-230/60/1

197/253

26.0

16.6

82.0

0.4

5.4

22.4

26.6

40

049

208-230/60/1

197/253

33.0

21.1

96.0

0.4

5.4

26.9

32.2

50

064

208-230/60/1

197/253

40.0

25.6

118.0

0.4

5.4

31.4

37.8

60

072

208-230/60/1

197/253

42.5

27.2

150.0

0.4

5.4

33.0

39.8

60

Rated Voltage of 208-230/60/1.

Rev.: 02/20/07

HACR circuit breaker in USA only.
Min/Max Voltage of 197/253.

All fuses Class RK-5.

Compressor

General

Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage

wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable. See unit electri-

cal data for fuse or cicuit breaker sizing information.
Electrical Data

Thermostat Wiring

Figure 3b: Thermostat Wiring for Dual Fuel Applications

Figure 3a: Thermostat Wiring

Electrical

Y1

Y2

O

R

C

C

R

Air Handler

Thermostat

24 VAC

Common

Common

24 VAC

Reversing Valve

2nd Stage Compressor

1st Stage Compressor

Y1

Y2

O

R

C

G

G

Fan

W

W

Typical EZ Wiring Diagram

P1

Air Handler transformer must be at least 75 VA.

L

Lo

Fault Signal

Envision Split

Y1

Y2

O

R

C

L

C

R

Fossil Fuel

Furnace

Thermostat

24 VAC

Common

Common

24 VAC

Fault Signal

Reversing Valve

2nd Stage Compressor

1st Stage Compressor

Y1

Y2

O

R

C

LO

G

G

Fan

W

W

Auxiliary Heat Relay

Note: Field installed DPST dual fuel relay

(Required for dual fuel installation)

Auxiliary Heat Relay

P2

P1

Shut

Down

= chassis

Envision Split

Auxiliary

Heat Relay

Advertising