background image

4. Troubleshooting (DeviceNet)

♦ Causes of Error

Possible Cause

Examination Method

Countermeasure

{ Master unit

configuration

(1)

Start applicomIO Console
application and check that the
configuration has no difference
with the network condition.

(2) Check that the configuration data

were written in flash.

(3) Check that the network load is

within allowable range.

z For details, refer to the section

4.1.3.6 EPSON RC+ Master
Configuration
.

Change the configuration.

{ Disconnected

terminating
resistors

{ Cable

disconnection

{ Disconnected

connector

{ Disconnected

signal wire

(1) Check that terminating resistors

are connected to both ends of the
network.

(2) Measure resistance between signal

wires with communications power
supply OFF.

→ Normal: 50 to 70

z Measuring point: Connection of the

trouble unit

z For detail, refer to the section

4.1.3.1 Connection Problem.

Fix the problem.

How to find the trouble
point:
Remove the terminating
resistor on one end of the
network. The trouble
point is where resistance
changes from 120

Ω.

{ Loose connector
{ Loose signal

wire

Check for the connection of connectors
and signal wires.
→ The connectors and signal wires

should be firmly connected.

z Checkpoint: all nodes and all branch

taps

z For details, refer to the section

4.1.3.2 Loose Connector and Signal
Wire
.

Connect the connectors
and signal wires again.

{ Voltage drop of

communications
power supply

Measure voltage of communications
power supply at the unit with a trouble.
→ Normal: 11V or more between V+

and V-

z If the voltage is 11 to 14 V, the unit

is a possible cause. Fix the problem
on the unit.

Check the voltage of the
power supply.
Calculate the current
capacity of the cable and
add more communications
power supplies.

{ Noise

(external cause)

Check the noise intrusion via the
following paths (1) to (3).
(1) Noise via DRAIN (FG)
(2) Induced noise via communication

cable

(3) Communications power supply
→ For details, refer to the section

4.1.3.3 Noise Intrusion.

Take countermeasures
against noise.

{ Broken unit

Replace the broken unit with a new
one.
→ Verify whether the problem is

fixed.

Replace the unit with a
new one.

z No cause is

identified.

Identify the trouble point by dividing
the network.
→ For details, refer to the section

4.1.3.4 Broken Unit Examination.

Fieldbus I/O Rev.6

93