Epson EM07ZS1647F User Manual

Page 34

Advertising
background image

2. Installation

PROFIBUS DP requires approximately 1ms at 12 Mbps for the transmission of 512 bits input
data and 512 bits output data distributed over 32 stations. The following figure shows typical
PROFIBUS DP transmission times depending on the number of stations and baud rate.

B

u

s C
ycle
T

im

e

[m

s]

500 kbps

1.5 Mbps

12 Mbps

Number of Slaves

2 10 20 30

18

14

10

6

2

The maximum cable length is restricted by the baud rate.

Baud Rate

Maximum Cable Length

12 Mbps

6 Mbps
3 Mbps

1500 kbps

500 kbps

187.5 kbps
93.75 kbps

19.2 kbps

9.6 kbps

100 m
100 m
100 m
200 m
400 m

1000 m
1200 m
1200 m
1200 m

Multi-Master Configuration

PROFIBUS DP allows you to install multiple masters on a single physical network.

All slave devices on the network can be accessed by different masters. Only one master on
the network can be used for device configuration.

The following figure illustrates the communication procedure for a multi-master
configuration.

Master 1

Master 3

Slave Slave Slave

Slave

Slave

Master 2

Slave

Slave

Token-passing Procedure

Master-slave communication

When the master receives the logic token, it inquires data from its slaves. After all
communications are completed, the master passes the token to another master. In this way,
the master can only communicate with its slaves while it is holding the token. The slaves
respond to only the inquiry from the master. No slave can output any messages.

22

Fieldbus I/O Rev.6

Advertising