Henny Penny BCM-110 User Manual

Page 9

Advertising
background image

Model BCF-24/65/110, BCM-110

1-4. ALARM MESSAGES

In the event of a system failure, the digital display will show an
alarm message. These messages are coded; “AL-1”, “AL-2”,
“AL-3”, “AL-5”, and “AL-6.” When an alarm occurs, the red
alarm LED will illuminate and a buzzer (optional) will sound. Press
the ALARM button to stop the buzzer.

The unit can operate on auto back-up if an alarm sounds for a
faulty probe. Must select the Timer Mode, and enter a time.

Display

Cause

Correction

“AL-1”

Faulty air temperature

Replace the probe; unit can operate on auto

probe

back-up until a new probe is installed

“AL-2”

Faulty evaporator probe

Replace the probe; the de-icing cycle can operate at
50% of the setting in step 7 of the Programming Section

“AL-3”

Faulty Frigiprobe

Replace the probe; the Frigiprobe Mode will not
operate, but the unit will operate in the Timer Mode

“AL-5”

Temperature too low

Faulty control board - replace control board;

in the hold mode

faulty contactor - replace contactor

“AL-6”

Temperature too high in

Faulty control board - replace control board;

the hold mode

door opened too much - make sure door stays
closed as much as possible

603