CT87A,B,J ROUND® THERMOSTAT

5

69-0274-6

1. Place the cover ring against the outlet box so that the arrow in the

middle of the cover ring is pointing up.

2. Pull the wires through the wiring hole on the bottom left side of the

cover ring.

3. Align the screw slots on the cover ring with the outlet box screw

holes, and attach the cover ring to the outlet box with two 1/2-in.

screws.

4. Place the wallplate or subbase over the cover ring so that the wiring

holes line up, and pull the wires through.

5. Loosely attach the wallplate/subbase to the cover ring with two 1/4-

in. screws, through the screw holes on the left and right sides of the

wallplate/subbase.

Level the wallplate or subbase

IMPORTANT: The wallplate/subbase must be level to maintain accu-

rate thermostat temperature.

1. Rotate the wallplate/subbase until level as shown in Fig. 6.

To level the subbase, use the leveling posts directly below the Heat

and Fan indicators.

Fig. 6. Leveling the wallplate.

2. Tighten the mounting screws after making sure that the wallplate or

subbase is level.

5

SPIRIT
LEVEL

LEVELING
POSTS (2)

MOUNTING
SLOTS

M3319A

OPENING FOR
THERMOSTAT
WIRING