Vent clearances and framing, A. pipe clearances to combustibles, B. wall penetration framing – Heat & Glo Fireplace HEAT & GLO SLR-B (COSMO) User Manual

Page 35

Advertising
background image

Heat & Glo • SLR-B • 2195-900 Rev. P • 12/11

35

* When using SLP pipe, minimum clearances from the vent pipe to combustible materi-

als at inside wall firestops are:

Top: 2-1/2 in. (64 mm)

Bottom: 1/2 in. (13 mm)

Sides: 1 in. (25 mm)

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).

‡

SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8 in. (111 mm to

194 mm thick).

‡,IZDOOWKLFNQHVVLVOHVVWKDQWKHH[LVWLQJKHDWVKLHOGVPXVWEHILHOGWULPPHG

,IZDOOWKLFNQHVVLVJUHDWHUWKDQLQD'93+60%ZLOOEHUHTXLUHG

(SLP Pipe Shown)

3 in. (76 mm)

top clearance *

1 in. (25 mm)

clearance

bottom & sides

Heat

Shield

Wall

Shield

Firestop

Heat

Shield

WALL

3 in. (76 mm)

top clearance

1 in. (25 mm)

clearance around

vertical sections

A. Pipe Clearances to Combustibles

WARNING! Risk of Fire! Maintain air space clearance to

vent.

DO NOT pack insulation or other combustibles:

• Between ceiling fi restops

• Between wall shield fi restops

• Around vent system
Failure to keep insulation or other material away from

vent pipe may cause over heating and fi re.

8

Vent Clearances and Framing

Figure 8.2 Wall Penetration

* Shows center of vent framing hole for top venting. The

center of the hole is one (1) in. (25.4 mm) above the

center of the horizontal vent pipe.

Figure 8.1 Horizontal Venting Clearances To Combustible

Materials

A*

B

48-1/16 in. 47-1/16 in.

A

10 in.

10 in.

B

DO NOT PACK WITH

INSULATION OR

OTHER MATERIAL

B. Wall Penetration Framing

Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must

frame a hole for the wall shield fi restop(s). The wall shield

fi restop maintains minimum clearances and prevents cold

air infi ltration.
• The opening must be framed on all four sides using the

same size framing materials as those used in the wall

construction.

• SLP pipe - A wall shield fi restop must be placed on each

side of an interior wall. A minimum 1-1/2 in. (38 mm)

overlap of attached heat shields must be maintained.

• See Section 10.K. for information for regarding the in-

stallation of a horizontal termination cap.

Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncom-

bustible materials such as concrete, a hole with diameter

one in. greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall

shield fi restop is only required on one side and no heat

shield is necessary.