Gas valve conversion, Figure 4, Changing pilot orifice – Honeywell PGF3 User Manual

Page 4: Figure 5 figure 6 burner pilot assembly, Typical gas valve honeywell sv9500, Figure 7

Advertising
background image

-- 4 --

462 06 1211 00

3/17/06

Manifold/Orifice Measurement

Measure 1

3

/16from face of orifice

to back edge of manifold pipe.

Figure 4

Changing Pilot Burner Orifice

(Required for Converting from Propane Gas

to Natural Gas) (All models except PGF3,

PGX3, and PDX3).

1. Disconnect the pilot supply line from the pilot burner.
2. Remove pilot orifice from pilot burner. Replace with natural

gas orifice stamped which is provided in kits (Figure 5)

3.. Reconnect the pilot tubing securely to the pilot burner.
4. Verify proper relationship of pilot burner assembly per fig-

ure 6, prior to completing the conversion.

Changing Pilot Orifice

Pilot

Orifice

Figure 5

Figure 6

Burner Pilot Assembly

Gas Valve Conversion

(Required for Converting

from Propane Gas to Natural Gas)

Conversion of Honeywell VR8200, SV9500,

SV9501 and

VR8204M Gas Valves using Natural Gas Conversion Kit #

396222.

1. Remove the regulator cap screw and pressure regulator ad-

justing screw. (See Figure 10)

2. Remove the existing regulator spring from the regulator

housing.

3. Insert the replacement spring (stainless steel) contained in

this kit into regulator housing.

Typical Gas Valve Honeywell

SV9500

WARNING

Explosion Hazard.

Serious injory or death

can result.

Read instructions before

operating valve.
Never

use tools to

operate valve

. Do not

disassemble valve. call a

qualified service technician

if the appliance does not

function properly.

Honeywell

CONTROL

IGNITER

OFF

ON

25-50-06

INLET

OUTLET

Pilot Adjustment

Pilot

Outlet

Wiring

Terminals

Outlet Pressure Tap

Connect manometer here to

check outlet pressure. Must be

adjusted per Table 1.