Max steady state input
current

62.5A per server blade enclosure installed at -
48VDC

Max steady state current
per feed/total

Power bus boxes

70 A/70A

Mini bus bars

210 A/210A

Scalable bus bars

210 A/350A or equivalent of 175A per feed*

In-rush current

In-rush current

In-rush current

In-rush current

Must support up to 2X the maximum operating current per server blade
enclosure (125 A) for up to 1.0 mS

Input over-current

Input over-current

Input over-current

Input over-current

Customer provided fusing for facility DC feeds that protects the system from
catastrophic over-current within 20 uS. Fuse should sustain all in-rush and
operating currents.

Max Input Current Slew

Max Input Current Slew

Max Input Current Slew

Max Input Current Slew
Rate

Rate

Rate

Rate

1A/uS

Max Rated Power

Max Rated Power

Max Rated Power

Max Rated Power

3000W per server blade enclosure

Connections and Cables

Connections and Cables

Connections and Cables

Connections and Cables Compaq provided facility DC cable connection kit:

The facility DC connection kit supports the connection of up to four -
48VDC, RETURN pairs and ground

The power cable assemblies consist of 1/0AWG, color-coded, flexible cable
rated at 105° C, terminated with bus mating connectors at one end and
unterminated at the other end. The cable length provided enables the
customer to route to a fuse panel within or adjacent to the rack.

NOTE:

NOTE:

NOTE:

NOTE: *All systems support redundant A and B feeds. Scalable bus bars support dual A and dual B
feeds.

** Periodic and random noise (PARD). Maximum allowable peak-to-peak ripple and noise (as measured
at the load on any output channel). The ripple and noise is measured over a 20 Hz to 100 MHz
frequency band. A resistive load (non-electronic) is used for this measurement. Each output is by-passed
to return by a 10uF tantalum capacitor with an ESR less than 100 milli-Ohms in parallel with a 0.47 uF
ceramic capacitor, at the point of load. The load cable is 12 feet of twisted wire capable of carrying the
current. The printed wiring board assembly is installed in its enclosure for this measurement, or the
measurement leads are properly shielded with Earth grounds applied to the insert.

© Copyright 2005 Hewlett-Packard Development Company, L.P.

The information contained herein is subject to change without notice.

Microsoft and Windows NT are US registered trademarks of Microsoft Corporation. Intel is a US registered trademark of Intel
Corporation.

The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and
services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial
errors or omissions contained herein.

QuickSpecs

HP ProLiant BL25p Server Blade

HP ProLiant BL25p Server Blade

HP ProLiant BL25p Server Blade

HP ProLiant BL25p Server Blade

Technical Specifications

DA - 12160 North America — Version 7 — June 27, 2005