Wiring and Electrical
following the wiring diagram, run all wires to their designated

connections. save the main power for the last hook-up,

and leave the breaker in the off position. The sensor wires

attach to the a350 Controller on the terminals marked “sen”

and “com”. Make sure the sensor is submerged fully into the

well and secured with the set-screws.
Setting The Aquastat
Inside the a350 control, you will see a square jumper, and

a differential dial. Be sure the jumper is in the “Heating”

position. The differential dial is set to determine how

low, below the temperature set point, you want the water

temperature to go before the automatic Draft Control

opens. a good initial setting for this dial is 5°. Be sure the

120V wires are attached to the common and the normally

open terminals, and replace the cover. The external dial is

set for the water temperature you wish to maintain, a good

setting is 180°.
Inside the Y350 control, ensure that your wires are

connected to the 120VaC terminals, and replace the cover.
Inside the s350 control, which is used as overheat

protection, you’ll see two dials; offset, and differential.

There is also a jumper which, in this case, gets placed in the

“cooling” position. The offset dial sets the number of degrees

above the a350 set point that you want the overheat dump

to activate. a good set point would be 20°. That would mean

that if the water reaches 200°, using the a350 set point of

180°, the s350 would close it’s contacts and energize the

overheat dump zone. The differential dial sets the point that

the overheat dump would stop. With the differential set at

15°, using the temperatures above, the circuit would re-

open, stopping the overheat dump at a water temperature

of 185°. The 120V wiring is attached on the normally open

and the common position. The normally closed position is

not used.
Re-install the covers onto the three Controls.

Optional Items
There is a domestic hot water coil available for your Trident

Boiler. The coil installs in the front of the boiler, and allows

your domestic water to be heated by the heating system

water. Install the coil now, by removing the round plate and

replacing it with the coil and it’s round plate. Be sure to

tighten the bolts evenly, to ensure a good seal.
If electric back-up is desired, install now. There will be two

additional control boxes to add to your aquastat, which will

require the use of a longer din rail. The two heating elements

will install into the front of the boiler as shown in fig. 1

Venting
The Harman® Trident Boiler must be installed into a chimney

approved for solid fuel burning appliances. In the U.s., the

boiler must be connected to; (1) a prefabricated chimney

complying with the requirements for Type HT chimneys in

the standard for Chimneys, factory Built, Residential Type

and Building Heating appliances, Ul 103. Or; (2) a code

approved masonry chimney with a flue liner. In Canada, with

prefabricated chimney systems tested and listed to the High

Temperature Chimney standard UlC s-629, or with a code

approved masonry chimney. The minimum recommended

height for any chimney is 16 ft. (4.8m) above the flue collar.

Do not reduce flue diameter. nominal size flue is 8 X 8 in.

or equivalent, up to 8 X 12 in. Codes also require that the

chimney must extend a minimum of

Installation