Duct work and operating instructions – Harman Stove Company SF2600A User Manual

Page 11

Advertising
background image



duct work and Operating Instructions

duct work.

This figure shows a typical duct

system layout. Be sure the entire sys-

tem is properly sized to provide the cor-

rect static pressure for optimum blower

performance. Have any new duct sys-

tem designed by a HVAC professional.

Operating Instructions

Adjusting Automatic draft

Control - In order for your new furnace

to function, the controls must be prop-

erly adjusted. The heat output is regu-

lated by the automatic draft control, on

the bottom door of the furnace. Refer to the illustrations at right; The electric draft

motor (A) opens and closes the flapper door (B). The flapper door opens to feed

more air to the fire and closes to reduce the air to the fire. The maximum air flow

can be adjusted by turning the adjuster bolt (C) counter-clockwise for more air and

clockwise for less air. NOTE: To preserve motor life, all adjustments of this bolt

should be done while the flapper door is in the closed position. The idle adjuster

(D) controls the minimum amount of air that enters the firebox when the flapper

door is closed. Adjustment is made by turning the adjuster vertical for zero air, or

horizontal for maximum idle air. It is best to start at a medium setting as shown at

right.

Adjusting the fan control- Shut off the power at the circuit breaker be-

fore removing the fan control cover. Make sure the copper jumper (circled below)

is removed before using the furnace. Note the three pointers on the dial. The one on

the right is the high limit adjustment. Pre-set at 00 degrees, it’s function is to close

the automatic draft control flapper door if the temperature in

the plenum reaches 00 degrees.

do not change this setting.

The center pointer adjusts the temperature at which the blower

starts. A good initial setting for this is 50 degrees. The pointer

on the left is to adjust the temperature at which the blower

stops. A good initial setting for this pointer is 00 to 0 degrees.

If it is set too low, the air will feel cool coming out of the registers

at the end of the blower cycle.

Thermostat- Set the thermostat to the desired tempera-

ture. When more heat is needed, the thermostat opens the au-

tomatic draft control flapper door. This allows air into the firebox,

which raises the output of the fire. When the temperature in the

plenum reaches the set temperature of the center pointer on the

fan control, the blower will begin blowing heated air through the

ductwork. When the thermostat reaches it’s setpoint, the automatic draft control closes

the flapper door, thus, reducing the output of the fire. As the temperature in the ple-

num drops to the set point of the left pointer on the fan control, the blower will stop. A

solid fuel fire cannot cease output immediately, therefore, your room temperature may

exceed the thermostat setting at times. You also may notice times that the blower runs

for a short period even though the draft control is closed. Again, you can’t just stop a

wood or coal fire instantly, and temperature may build enough to run the blower. This is

normal and will be noticed more with coal than with wood.

mEd

mAX

zErO

return Air

Supply Trunk

Plenum

Figure 5

Figure 6

Figure 7

Advertising
This manual is related to the following products: