WSK-24 WIRELESS OCCUPANCY SOLUTION

INSTALLATION

62-0300ES—01

4

Fig. 3. Receiver and wiring harness.

Using Table 3 on page 3 and Fig. 3, wire the harness to
the thermostat and connect the harness to the receiver.

1. Wire the red and white power leads on the wiring

harness into the power terminals on the thermostat.

2. Wire the white/brown and brown dry contact leads

on the wiring harness into the remote setback
terminals on the thermostat.

3. Plug the wiring harness into the receiver. The

harness is keyed and fits only one way.

4. Supply power to the thermostat.
5. The LED on the receiver flashes twice to show it

has power.

6. Continue with “Setting the Delay on the Receiver”.

Setting the Delay on the Receiver

Refer to Fig. 4 and position the jumper to the desired
delay option:

Position the jumper near the pushbutton:

— Front Door - 3 minute delay
— 2nd optional door - 1 minute delay

Position the jumper away from the pushbutton (default
position):

— Front Door - 15 second delay
— 2nd optional door - 1 minute delay

The receiver delay and the delay that is programmed in
the thermostat will be combined to provide an overall
delay.

Mounting

Mounting the Receiver

The receiver can be mounted behind the thermostat in the
wall, inside the fan coil unit, or mounted on the wall.

Mounting screws or double-sided adhesive tape can be
used to mount the receiver.

Fig. 4. Receiver components.

Mounting the Door Sensor

1. Remove battery tab before installation. See Fig. 5.

Fig. 5. Battery tab removal.

2. Remove the plastic mounting bracket from the door

sensor housing.

3. Place the mounting bracket for the door sensor high

on the frame of the front door. Secure the bracket to
the door frame by using the two screws or adhesive
tape provided. See Fig. 6 on page 5.

M29150

TO THERMOSTAT

WIRING

HARNESS

RECEIVER

ANTENNA

1. WIRE RED AND WHITE WIRES TO

24 VAC POWER AND COMMON.

2. WIRE WHITE/BROWN AND

BROWN WIRES TO DRY CONTACT

TERMINALS

ON

THERMOSTAT.

M29151

TOP END VIEW

BOTTOM END VIEW

JUMPER

PUSHBUTTON

WIRING

HARNESS

CONNECTOR

LED

PULL OUT

BEFORE USE

M29152