Hampton H300 Cast Freestanding Woodstove

10

FLOOR PROTECTION

A combustible fl oor must be protected by non-combustible material (like tile, concrete board, or certifi ed to UL-1618 or as defi ned by local codes)
extending beneath the heater and a minimum of 6" from each side and minimum 18" from the front face of the stove and minimum 6" (or the rear
clearance to combustibles whichever is smaller) from the rear of the stove.

When installed with horizontal venting, non-combustible fl oor protection must beneath the fl ue pipe and extend 2" (51mm) beyond each side.

NOTE: In Canada, fl oor protection must

extend 18" (450mm) to the front
and 8" (200mm) to each side and
back of the stove.

Minimum Overall Depth (Y) of Floor Protector

Residential Residential Mobile Home Alcove

Unit "C" Vent Close Clearance Close Clearance

Y Z

Y

Z

Y Z

Y

Z

H300 (US)

44-1/2" 6" (152 mm) 44-1/2" 6" (152 mm) 44-1/2" 6" (152 mm) 44-1/2" 6" (152 mm)

(1130 mm)

(1130 mm) (1130 mm)

(1130 mm)

H300 (Canada)

46-1/2" 8" (203 mm) 46-1/2" 8" (203 mm) 46-1/2" 8" (203 mm) 46-1/2" 8" (203 mm)

(1181 mm)

(1181 mm) (1181 mm)

(1181 mm)

INSTALLATION

IF SIDE LOAD DOOR IS USED:

Floor protection must extend 18" (457mm)

from the side of the unit to the wall.

Floor protection must be a minimum of 3/8"

thick with a minimum k factor of 0.84.


Minimum Overall Width (X) of Floor Protector
for all installations:

H300 39"

(990

mm)

-

US

43"

(1092mm)

-

Canada