Hampton H300 Cast Freestanding Woodstove

14

INSTALLATION

RECOMMENDED HEIGHTS FOR

WOODSTOVE FLUE

Simple rules on draft. See Table 1.

1) At sea level minimum height is 12'

straight.

2) Add the following vertical height to compen-

sate for:

45 deg. elbow = 1 ft.

90 deg. elbow = 2 ft.

"T"

= 3 ft.

Each foot of horizontal run = 2 ft.

3) Add 4% overall for each 1000' above sea

level.

Example: a)

1-1/2 ft. of horizontal run

= 3 ft.

one "T"

= 3 ft.

Total Addition (at sea level)

= 6 ft.

Example: b)

One 90 deg. elbow

= 2 ft.

2 ft. of horizontal run

= 4 ft.

one "T"

= 3 ft.

Total Addition (at sea level)

= 9 ft.

Recommended Flue Height
Elevation Example a) Example b)
0' 18'

21'

1000'

18.72'

21.84'

2000'

19.44'

22.68'

5000'

21.60'

25.20'

8000'

23.76'

27.72'

TABLE 1

MINIMUM RECOMMENDED FLUE HEIGHTS IN FEET

(Measured from the top of the unit)

# OF ELBOWS

ELEVATION (FT)
ABOVE SEA LEVEL
0 2 x 15

o

4 x 15

o

2 x 30

o

4 x 30

o

2 x 45

o

4 x 45

o

0-1000

12.0

13.0

14.0

15.0

18.0

16.0

20.0

1000-2000

12.5 13.5 14.5 15.5 19.0 16.5 21.0

2000-3000

13.0 14.0 15.0 16.0 19.5 17.0 21.5

3000-4000

13.5 14.5 15.5 17.0 20.0 18.0 22.5

4000-5000

14.0 15.0 16.0 17.5 21.0 18.5 23.0

5000-6000

14.5 15.5 17.0 18.0 21.5 19.0 24.0

6000-7000

15.0 16.0 17.5 18.5 22.5 20.0 25.0

7000-8000

15.5 16.5 18.0 19.0 23.0 20.5 25.5

8000-9000

16.0 17.0 18.5 20.0 24.0 21.0 26.5

9000-10000

16.5 17.5 19.0 20.5 24.5 22.0 27.0

NOTE: No more than two offsets (four elbows) allowed. Two 45

o

elbows equal one 90

o

elbow.