Vent clearances and framing, A. pipe clearances to combustibles, B. wall penetration framing – Heat & Glo Fireplace XLR-N-CE User Manual

Page 30

Advertising
background image

Heat & Glo • XLR-N-CE, XLR-PB-CE • 2198-900 Rev. L • 3/13

30

Note: Heat shields MUST overlap by a minimum of 38 cm.

SLP heat shield - designed to be used on a wall 11,1 cm to 19,4 cm thick.

• If wall thickness is less than 11,1 cm the existing heat shields must be field tricmed.

If wall thickness is greater than 19,4 cm a DVP-HSM-B will be required.

6,4 cm

top clearance

1,3 cm

clearance

bottom & sides

2,5 cm

bottom

clearance

Heat

Shield

Wall

Shield

Firestop

Heat

Shield

WALL

7,6 cm

top clearance

2,5 cm

clearance around

vertical sections

A. Pipe Clearances to Combustibles

WARNING! Risk of Fire! Maintain air space clearance to

vent.

DO NOT pack insulation or other combustibles:

• Between ceiling firestops

• Between wall shield firestops

• Around vent system
Failure to keep insulation or other material away from

vent pipe may cause over heating and fire.

8

Vent Clearances and Framing

Figure 8.2 Wall Penetration

* Shows center of vent framing hole for top venting. The center of the hole

is one 2,54 cm above the center of the horizontal vent pipe.

Figure 8.1 Horizontal Venting Clearances To Combustible

Materials

A*

B

122 cm

120 cm

A

25,4 cm

25,4 cm

B

DO NOT PACK WITH

INSULATION OR

OTHER MATERIAL

B. Wall Penetration Framing

Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must

frame a hole for the wall shield firestop(s). The wall shield

firestop maintains minimum clearances and prevents cold

air infiltration.
• The opening must be framed on all four sides using the

same size framing materials as those used in the wall

construction.

• SLP pipe - A wall shield firestop must be placed on each

side of an interior wall. A minimum 3,8 cm overlap of at-

tached heat shields must be maintained.

• See Section 10.K. for information for regarding the in-

stallation of a horizontal termination cap.

Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncom-

bustible materials such as concrete, a hole with diameter

2,54 cm greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall

shield firestop is only required on one side and no heat

shield is necessary.