Chapter 9: 6801PS-48 Power Supply Module

Installing the 6801PS-48

40

6800/7000 Series - Frames and Power Supplies Installation and Operation Manual

Installing the 6801PS-48

Precautions

To reduce the risk of electric shock or energy hazards, heed the following
cautions:

• Connect the 6801PS-48 to a reliably grounded SELV source or a

centralized DC source.

• The branch circuit overcurrent protection must be rated a

maximum 10 A circuit breaker in series with a maximum 5 A
listed fuse. (

See

suggested protection devices on page 41.)

• Use 14 AWG solid copper conductors only.

• A readily accessible disconnect device that is suitably approved

and rated, shall be incorporated into the field wiring. (

See

suggested breaker switch type on page 41.)

• To be installed in a restricted access area in accordance with the

NEC or the authority having jurisdiction.

To reduce the risk of electric shock, heed these cautions:

• Perform installation and exchange only if you are a trained

technician who is familiar with these instructions and aware of
the shock hazards of working with live equipment.

• Install the 6801PS-48 power supply in accordance with the

schematic diagram shown on page 41.

• Power can only be disconnected completely from the 6800/7000

series frame through a studio installed breaker or fuse.