Dvp, sl-d and sl-flex series venting – Hearth and Home Technologies BE-36-CIPI User Manual

Page 25

Advertising
background image

Hearth & Home Technologies • BE-36-C, BE-36-CIPI • 397-981 Rev. R • 2/05

25

For Vertical Runs - One ceiling firestop is REQUIRED at
the hole in each ceiling through which the vent passes.

To install firestops for vertical runs that pass through ceilings:

• Position a plumb bob directly over the center of the verti-

cal vent component.

• Mark the ceiling to establish the centerpoint of the vent.

• Drill a hole or drive a nail through this centerpoint.

• Check the floor above for any obstructions, such as wir-

ing or plumbing runs.

• Reposition the fireplace and vent system, if necessary,

to accommodate the ceiling joists and/or obstructions.

• Cut a 10-inch X 10-inch (254mm X 254mm) hole through

the ceiling, using the centerpoint previously marked.

• Frame the hole with framing lumber the same size as the

ceiling joists.

NOTE: There must be NO INSULATION or other
combustibles inside the framed firestop opening.

Figure 22 Hole & New Framing Members

CEILING

NEW
FRAMING
MEMBERS

EXISTING CEILING
JOISTS

CHIMNEY
HOLE

10" (254mm)
10"

(254mm)

• Position the firestops on both sides of the hole previ-

ously cut and secure the firestops with nails or screws.

• The heat shields of the firestops MUST BE placed to-

wards the top of the hole.

• Continue the vent run through the firestops.

Figure 20. Hole and Vent Pipe

Figure 21. Heat Shield, Interior & Exterior Firestops

TRIM HEAT
SHIELD IF TOO
LONG, ADD TO
SHIELD IF TOO
SHORT

EXTERIOR
FIRESTOP

INTERIOR

FIRESTOP

HEAT SHIELD

DVP, SL-D and SL-Flex Series Venting:

STEP 4. Install Firestops

For Horizontal Runs - Firestops are REQUIRED on both
sides of a combustible wall through which the vent passes.

NOTE: Model DVP-TRAP or SLK-01TRD does not need
an exterior firestop on an exterior combustible wall.

To install firestops for horizontal runs that pass through
either interior or exterior walls:

Cut a 12” x 10“ (305mm x 25mm) hole through the wall for
DVP-series or a 10” x 10” (254mm x 254mm) hole for SL-D-
series pipe. The center of the framing hole is one (1) inch
(25.4mm) above the center of the horizontal vent pipe.

VENT PIPE

1" (25.4 mm)

12"(DVP) or 10" (SL)

(305mm or 254mm)

10"

(254mm)

NOTE: There must be NO INSULATION or other
combustibles inside the framed firestop opening.