C645A-E PRESSURE SWITCHES

The C645E1002 Distillate Fuel Oil Pressure Switch is the
same as the C645A1006 Gas Pressure Switch except that it
does not have a 0.015 in. (0.38 mm) diameter (nominal)
orifice in its 1/4 in. NPT main (high pressure) connection.
(This orifice is required in a C645A Gas Pressure Switch to
restrict gas leakage, but it is too small for oil applications.)
The C645E1002 has a 0.125 in. (3.18 mm) diameter
(nominal) opening in its 1/4 in. NPT main connection into its
pressure chamber.

CAUTION

Vent the bleed tapping back to the oil supply tank—
not to the combustion chamber.

Wiring

Disconnect power supply before connecting wiring to prevent
electrical shock and equipment damage.

All wiring must agree with applicable codes, ordinances, and
regulations. An opening is provided to accommodate rigid
conduit or armored cable for line voltage operation (Fig. 3
and 4). Do not overload the switch contacts (see Switch
Ratings in Specifications section). The switching schematic is
shown in Fig. 5.

SET POINT
ADJUSTMENT
SCREW

SCALE
PLATE

BLEED
FITTING

COVER
SCREW

OPENING
FOR 1/2 INCH
CONDUIT

MICRO
SWITCH

MANUAL RESET LEVER
ON LOCKOUT MODELS ONLY

M7560

Fig. 3. C645A,B,D with cover removed.

M7561

SET POINT
ADJUSTMENT
SCREW

SCALE
PLATE

BLEED
FITTING

COVER
SCREW

OPENING
FOR 1/2 INCH
CONDUIT

MANUAL RESET
LEVER
ON LOCKOUT
MODELS ONLY

Fig. 4. C645C with cover removed.

Fig. 5. Schematic showing switch in zero

pressure condition.

1

1

2

2

W

B

R

C645A,C,D BREAKS R-W, MAKE R-B ON PRESSURE FALL.
MANUAL RESET MODELS LOCK OUT.

C645B BREAKS R-B, MAKES R-W ON PRESSURE RISE
AND LOCKS OUT.

M7565