C645A-E PRESSURE SWITCHES

SETTINGS AND ADJUSTMENTS

Pressure Setpoint Adjustment

Tables 2 through 4 give the pressure and switching for each
setpoint. To adjust the pressure setting, turn the setpoint
adjustment screw (Fig. 3 and 4) clockwise to increase
the pressure setting and counterclockwise to decrease
the pressure setting.

Table 2. C645A,D,E control points.

Setpoint

Switching

Pressure

in. of Water

Pressure

kPa

3

a

R-W makes

3

0.8

R-B makes

2

0.5

9

b

R-W makes

9

2.2

15

b

R-W makes

15

3.7

21

c

R-W makes

21

5.2

R-B makes

18

4.5

35

d

R-W makes

35

8.7

R-B makes

31

7.7

a

Nominal differential—1 in. of water (0.2 kPa).

b

Differential between 1 and 3 in. of water (0.2 and 0.7 kPa).

c

Maximum differential—3 in. of water (0.7 kPa).

d

Maximum differential—4 in. of water (1.0 kPa).

Table 3. C645B control points.

Setpoint

Switching

Pressure

in. of Water

Pressure

kPa

3

a

R-W makes

3

0.8

R-B makes

2

0.5

9

b

R-W makes

9

2.2

15

b

R-W makes

15

3.7

21

c

R-W makes

21

5.2

R-B makes

18

4.5

35

d

R-W makes

35

8.7

R-B makes

31

7.7

45

e

R-W makes

45

11.2

R-B makes

39

9.8

a

Nominal differential—1 in. of water (0.2 kPa).

b

Differential between 1 and 3 in. of water (0.2 and 0.7 kPa).

c

Maximum differential—3 in. of water (0.7 kPa).

d

Maximum differential—4 in. of water (1.0 kPa).

e

Maximum differential—5.7 in of water (1.4 kPa).

a

Nominal differential—0.2 in. of water (0.05 kPa).

b

Differential between 0.2 and 0.8 in. of water (0.05 and
1.2 kPa).

c

Maximum differential—0.8 in. of water (0.2 kPa).

C645B1047 Scaleplate Stop Adjustment

The C645B1047 is the same as the C645B1013 except for a
scaleplate stop.

Specifications

Scaleplate Stop:
Limits maximum setting, factory-set at 5-1/4 in. of water
(1.31 kPa).

Scale Range:
3 to 21 in. of water (0.75 to 5.23 kPa).

Adjusting Wrench:
Part no. 23466 included with the C645B1047.

To Adjust Scaleplate Stop

Remove cover.

Loosen scaleplate stop locking screw about 1/2 turn
counterclockwise with the 23466 Adjusting
Wrench.

Move scaleplate stop until

bottom

edge is aligned with

desired maximum setting.

Tighten scaleplate stop locking screw clockwise .

Replace cover.

Table 4. C645C Control Points.

Setpoint

Switching

Pressure

in. of Water

Pressure

kPa

1

a

R-W makes

1

0.25

R-B makes

0.8

0.2

3

b

R-W makes

3

0.75

R-B makes

2.6

0.64

5

b

R-W makes

5

1.24

R-B makes

4.3

1.2

Top Scale

c

R-W makes

6

1.50

R-B makes

5.2

1.3