5

69-0637—2

Fig. 10—Temperature control levers.

HEATING/COOLING SYSTEM

Turn on power to the furnace and cooling system.
Place the system switch lever to HEAT and fan switch

lever to AUTO.

Push both temperature setting levers together at least

5

°F (3°C) above room temperature. The main burner should

come on. The fan will start when the furnace heats up. (If
central electric heat or heat pump system, fan starts imme-
diately.)

Move both levers 5

°F (3°C) below room temperature.

The burner should shut off.

Place the system switch lever at COOL and the fan

switch lever at AUTO. The cooling equipment should
operate, and the fan will start. Allow for any time delay that
may be built into the compressor control circuit.

NOTE: To avoid compressor damage, do not operate the

system if outdoor temperature is below 50

°F (10°C).

Refer to manufacturer recommendations.

Move both temperature setting levers together at least

5

°F (3°C) above room temperature. The cooling equipment

should shut off.

Place the fan switch to ON. The fan should run continu-

ously with the system switch in any position.

Place the system switch to OFF. Move both temperature

setting levers to various positions. The heating and cooling
systems should not operate.

Operate the entire system for at least one complete cycle

with the system switch at COOL and one complete cycle
with the switch at HEAT.

If thermostat fails any test, refer to the Troubleshooting

Guide in the Owner’s Manual.

Reset both temperature setting levers to the desired

temperatures.

Leave Owner’s Manual and Assistance Information in a

convenient place for the building occupant or provide with
other appliance manuals.

TYPICAL WIRING DIAGRAMS

For wiring, follow the hookup diagram supplied with

your heating, cooling or heating/cooling equipment. If not
available, use Fig. 11 as a guide.

REMEMBER: Your wiring must follow local electrical

codes and ordinances.

50

60

70

80

HIGH TEMPERATURE
(RED MARK)
SET LEVER

LOW TEMPERATURE
(BLUE MARK)
SET LEVER

M859

SET SUBBASE SWITCHES

The subbase system switch controls system operation as

follows:

HEAT: Heating system is controlled by the thermostat.

Cooling system is off.

COOL: Cooling system is controlled by the thermostat.

Heating system is off.

OFF: Both the heating and cooling systems are off. If the

fan switch is in the AUTO position, the fan is also off.

The subbase fan switch controls fan operation as follows:
ON: Fan operates continuously.
AUTO: Fan operates with the cooling equipment as

controlled by the thermostat or with the heating equip-
ment as controlled by the plenum switch. In electric
heat, heat pump and fan coil systems, the fan is
controlled by the thermostat in heating and cooling.

To switch positions, use thumb or index finger to slide

lever to the desired position. Switch lever must stop in
detent over the desired function indicator mark for proper
circuit operation.

CHECK OUT THERMOSTAT OPERATION

CAUTION

Do NOT check operation by shorting across
terminals of relay or valve coil; this will burn
out the thermostat heat anticipator.