SECTION V TROUBLESHOOTING GUIDE


All Herrmidifier 6000 Series Humidifiers are

manufactured under strict quality control and are

subjected to a complete operational test. All circuit board
adjustments are made at the factory and should not be

adjusted beyond the guidelines set in this

troubleshooting guide without first consulting a factory
representative. The following information is for your help

and reference. If you still experience difficulty after trying

these remedies, contact your Herrmidifier representative.

TEST POINTS

Each circuit board (See Figure 12) features three test

points to aid in the troubleshooting process. Each of
these test points works on a 0-4 VDC scale. “0 VDC” =

0%. “4 VDC” = 100%. All readings are between the test

point and ground (Molex J1, terminal 11 [far right of
molex connector, hours wire #11]).

Test Point #1:
Provides exact reading of drain threshold setting.

Test Point #2:
Provides circuit board reference voltage. Should always

read 4 VDC +/-2%.


Test Point #3:

Provides actual percentage of output. For example, a

unit running at 80% of maximum output would have a
Test Point #3 to ground reading of 3.2 VDC.



Maximum Capacity Setpoint
The potentiometer labeled “R39" located in the top left-

hand corner of the board allows adjustment of the unit's

capacity in the range of 50-100% of maximum.

Circuit Board Settings

Models Time

Cycle

R23

Low Drain

Setting,

R18

Capacity,

R39

Standard Settings

All 60

sec 90 100%

High Conductivity Settings

(over 1000 micromhos)

All 84

sec 93 90%

Softened Water Settings

(750-1000 micromho)

All 60

sec 92 95%

Low Conductivity Settings

(<100 micromho)

All 60

sec 85 100%

NOTE

All blower units have their capacity set from the
factory at 4 lbs/hr. These units can have their
capacity increased by increasing the capacity
adjustment potentiometer. Ensure there is
sufficient air circulation in the conditioned space
to prevent condensation on walls or ceiling
when increasing capacity beyond 4 lbs/hr.

WARNING!

The Herrmidifier 6000 Series Electronic Steam
Humidifier cabinet was designed to house and
shield the components from outside
interference. Absolutely NO other components
may be mounted inside or be electrically tapped
into the humidifier without Herrmidifier's express
written permission. Failure to heed this warning
will void your warranty.