Steam Distribution

Blower Version (6000-1,2)

The 6000 Series Steam Humidifier with the built in
blower pack should be mounted a minimum of 18” from

the ceiling. There should also be 5' of horizontal

clearance in front of the unit to prevent stem from
condensing on obstructions (See Figure 1). There is an

adjustable louver to adjust the direction of the steam

plume.

DUCTED VERSION (6000-3,4)

Herrmidifier supplies a stainless steel duct distributor for
injecting pure steam into the duct. This can be installed

in the bottom or the side of the duct (See Figure 5).

When installing in the side of the ductwork make sure it
is positioned to allow condensate to drain back down the

steam hose. The duct distributor pipe has a built in pitch

to allow condensate to drain back into the hose. The
hose must be installed with a minimum 8% (1” per foot)
pitch back to the humidifier to allow condensate to drain

back to the steam cylinder (See Figures 5 & 6). A
minimum of 5 feet downstream clearance before any

bends or obstructions is recommended for most

applications (See Figure 2). However, different
psychrometric conditions may require greater or lesser

steam absorption distances. A minimum duct

temperature of 60 degrees F is recommended.
Temperatures below this may cause condensation to

form in the duct. Lined duct may be used if the thickness

is 1” or less.

Distributor Mounting Instructions
Sheet metal Duct:
Make a 1-1/4" hole in the duct at desired location. Insert
duct distributor and secure with self-tapping sheet metal
screws (supplied by others).

WARNING!

Do not adjust this louver to extreme angles as it
will restrict the airflow causing condensation to
form around the steam distribution manifold.


Fiberboard Duct:
Make a 1-1/4" hole in the duct at desired location. Insert
duct distributor and mark the four holes on flange. Drill
(4) ¼”- holes at marked locations. Cut an access hole in
duct and install the enclosed tee nuts from the inside of
the duct. Fasten distributor with enclosed ¼” bolts.

WARNING!

Locate away from areas where people can walk
into steam path.

Figure 6

Figure 5