Key Features

Adjustable Setpoints

Capacity
• Range = 50-100%
• Preset at 100% for 6000-1,3,4

Preset at 50% for 6000-2

Low Drain Threshold
• Range = 50-100%
• Preset at 90%

Cycle Time
• Range = 60-300 seconds
• Preset at 60 seconds

Faults

Overcurrent
• 138% of Rated Current
• System Shutdown



Fill System
• Fill valve open for 6 hours without achieving capacity setpoint or cylinder full
• System Shutdown

End of Cylinder Life
• 6 hours of operation while on cylinder full without achieving capacity setpoint
• System Shutdown (See Pg. 14 for Manual Override)

Conductivity*

Micromhos

(approx.)

Average Life**

Expectancy – Hrs.

(approx.)

100 2000

135 1900

170 1800

250 1300

500 800

750 650

1000 500

*If the conductivity of your supply water is less than 100 micromho, consult Herrmidifier for specific circuit board

adjustments and replacement tank information (GT-176-1).

Unit performance may be affected.

Operation on water of less than 60 micromho is not recommended.

**Your actual cylinder life may be higher or lower depending on the exact composition of your water supply.