Table 4. Terminal Designations and Descriptions.

Fig. 4. Proper wiring technique.

Mounting Thermostat Wallplate

The thermostat mounts on the wallplate after they are
installed.

1. Engage tabs at the top of thermostat and wallplate.

See Fig. 5.

2. Press lower edge of case to latch.

NOTE:

To remove the thermostat from the wall, first pull out
at the bottom of the thermostat; then remove the top.

Fig. 5. Mounting thermostat on wallplate.

Standard

Terminal

Designations

Alternate

Terminal

Designations

Typical Connection

Function

Terminal Type

B

Heat damper or changeover valve

Output

24V powered contact

C

B

a

, C, X1, X2

Common

Input

G

F

Fan relay

Output

24V powered contact

O

R

Cool damper or changeover valve

Output

24V powered contact

OT, OT

Outdoor temperature sensor (C7089B)

Input

R

V

24V system or heating transformer

Input

RC

24V cooling transformer

Input

W1

H1, R3

Stage 1 heating relay

Output

24V powered contact

W2

H2, R4, W3, Y

Stage 2 heating relay

Output

24V powered contact

Y1

C1, M, Y

Stage 1 compressor contactor

Output

24V powered contact

Y2

C2, M, Y

Stage 2 compressor contactor

Output

24V powered contact

a

Some OEM models label the terminal for transformer common B.

M4826

FOR WRAPAROUND
INSERTION STRIP
7/16 IN. (11 MM).

FOR STRAIGHT
INSERTION STRIP
5/16 IN. (8 MM).

M15043

B.

PRESS LOWER EDGE OF CASE TO LATCH.

A.

ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE.