Table 6. Thermostat Installer Setup Options (continued).

IMPORTANT

Review the settings to confirm that they match the
system. Press Run Program to exit the Installer
Setup. The thermostat has saved the Installer Setup
changes and initiated a reset in order to operate with
these new settings. Be sure to set the current day
and time immediately.

Setting Current Day and Time

1. Press Set Current Day/Time.

NOTE:

On initial power up or after an extended power
loss, 1:00 pm flashes on the display until a key
is pressed.

M10312

Time

Set Program

System

Fan

Run

Program

Hold Temp

Set Current

Day/Time

Set Current

Day/Time

Wake

Leave

Return

Sleep

Day

Heat/Cool

Settings

Daylight

Time

Copy

Mon

PM

Set Day/Time

Installer Setup

Number (Press

Time

key to

Factory-Setting

Other Choices

(Press

or

key to change)

Actual

Select

change)

Display

Description

Display

Description

Setting

Not used

31 and 32

Minimum off time
for the compressor

33

5

5 minute minimum off
time for the
compressor

0 thru 4

Minimum number of minutes
(0 thru 5) the compressor will
be off between calls for the
compressor

Temperature range
stops in heating

34

90

Highest setpoint
heating can be set to

40 to 89

Temperature range (1°F
increments) heating setpoint
can be set to

Temperature range
stops in cooling

35

45

Lowest setpoint
cooling can be set to

46 to 99

Temperature range (1°F
increments) cooling setpoint
can be set to

Not used

36

Temperature
display adjustment

37

0

No difference in
displayed temperature
and actual room
temperature

-3 thru 3

1—Display adjusts to 1°F

higher than actual room
temperature

2—Display adjusts to 2°F

higher than actual room
temperature

3—Display adjusts to 3°F

higher than actual room
temperature

-1—Display adjusts to 1°F

lower than actual room
temperature

-2—Display adjusts to 2°F

lower than actual room
temperature

-3—Display adjusts to 3°F

lower than actual room
temperature

Advertising