D. Chimney Termination Requirements

Follow manufacturer’s instructions for clearance, securing
flashing and terminating the chimney.

Must have an approved and listed cap

Must not be located where it will become plugged by

snow or other material

• Must terminate at least  feet (91cm) above the roof

and at least 2 feet (61cm) above any portion of the

roof within 10 feet (05cm).

• Must be located away from trees or other struc-

tures

These are safety requirements and are not meant to assure proper flue draft.

Figure 17.1

E. 2-10-3 Rule

Figure 17.2

NOTE:
• Chimney performance may vary.
• Trees, buildings, roof lines and wind conditions affect

performance.

• Chimney height may need adjustment if smoking or

overdraft occurs.

3 ft. (91cm)

Minimum

Less than 10 ft. (305cm)

2 ft. (61cm)

3 ft. (91cm)

Minimum

10 ft. (305cm) To Nearest Roofline

2 ft. (61cm)

Pitched Roof

10 ft. (305cm) or more

3 ft. (91cm) Minimum

Less than 10 ft. (305cm)

2 ft. (61cm)Minimum

3 ft. (91cm) Minimum

Wall or Parapet

Flat Roof