Hearth and Home Technologies VRT-GY-P-CE User Manual

Page 9

Advertising
background image

9

Heat & Glo • VRTIKL-CE • 7031-292 Rev E • 12/07

V

= VENT TERMINAL

X

= AIR SUPPLY INLET

= AREA WHERE TERMINAL IS NOT PERMITTED

Figure 4.4 Minimum Clearances for Termination

A

= 31 cm ....................clearances above grade, veranda,

porch, deck or balcony

B =

31

cm

....................clearances to window or door

that may be opened, or to perma-
nently closed window. (Glass)

D*

= 31 cm ....................vertical clearance to unventilated

soffi t or to ventilated soffi t located
above the terminal

76 cm .....................for vinyl clad soffi ts and below

electrical service

F

= 23 cm ...................clearance to outside corner

G

= 15 cm ....................clearance to inside corner

H

= 91 cm ....................not to be installed above a gas

meter/regulator assembly within 90
cm horizontally from the center-line
of the regulator

I =

1.8

M

.....................clearance to gas service regulator

vent outlet

J =

31

cm

......................clearance to non-mechanical

air supply inlet to building or the
combustion air inlet to any other
gas stove

K =

1.8

M

.......................clearance to a mechanical

(powered) air supply inlet

L** = 2.1

M

.......................c l e a r a n c e a b o v e p a v e d

sidewalk or a paved driveway
located on public property

M*** = 46 cm ......................clearance under veranda, porch,

deck, balcony or overhang

1.1 M ......................vinyl

** a fl ue shall not terminate directly above a sidewalk or paved driveway

which is located between two single family dwellings and serves both
dwellings.

*** only permitted if veranda, porch, deck or balcony is fully open on a

minimum of 2 sides beneath the fl oor, or meets Note 2.

NOTE 1: On private property where termination is less than 7 feet above
a sidewalk, driveway, deck, porch, veranda or balcony, use of a listed cap
shield is suggested. (See fl ue components page)

NOTE 2: Termination in an alcove space (spaces open only on one side
and with an overhang) are permitted with the dimensions specifi ed for vinyl
or non-vinyl siding and soffi ts. 1. There must be 2.7M minimum between
termination caps. 2. All mechanical air intakes within 3M of a termination
cap must be a minimum of 2.7M below the termination cap. 3. All gravity
air intakes within 2.7M of a termination cap must be a minimum of .31M
foot below the termination cap.

(See Note 1)

(See Note 1)

(See Note 2)

NOTE 3: Local codes or regulations may require different
clearances.

NOTE 4: Termination caps may be hot. Consider their proximity to
doors or other traffi c areas.

NOTE 5: Location of the fl ue termination must not interfere with
access to the electrical service.

Heat & Glo assumes no responsibility for the improper performance
of the gas stove when the fl ueing system does not meet these
requirements.

Q

MIN

= # termination caps x 3 R

MAX

= (2 / # termination caps) x Q

ACTUAL

Alcove Applications

S = 15 cm .......................clearance from sides of elec-

trical service

T = 31

cm

........................clearance above electrical

service

(See Note 5)

(See Note 5)

See Notes 3 & 4

Electrical

Service

V

S

V

S

V

T

D*

V

M

N

P

R

Q

Q

MIN

R

MAX

1 cap

.91 M

2 x Q

ACTUAL

2 caps

1.8 M

1 x Q

ACTUAL

3 caps

2.7 M

2/3 x Q

ACTUAL

4 caps

3.7 M

1/2 x Q

ACTUAL

N

= 15 cm .....................non-vinyl sidewalls

31 cm .....................vinyl sidewalls

P =

2.4

M