AQUATROL ZONE SYNCHRONIZING BOILER RESET CONTROLS

3

69-1979—04

LCD Display Panel Layout

The LCD on the AQ251 Control Panel is used to:

— Monitor system status and performance.

— Select and/or modify control settings for the hydronic

system.

— Diagnose and troubleshoot system problems.

The layout of the display is logical and simple to navigate. The

information displays so that you can see at a glance the

system’s operating temperatures, as well as the status of the

system equipment, such as a call for heat, DHW pump ON,

Boiler T-T terminals energized, etc. Fig. 1 on page 2 illustrates

the layout and features of the LCD display panel and keypad.

LCD Display Navigation

This section describes how the keypad is used to navigate the

LCD display and menus.
• The LCD displays up to three lines of text at a time. For

menus with more than three lines, use the up and down

buttons (

^

or v) to scroll through the menu options.

• As the menu is scrolled up or down, the indicator arrow

(←)

shows which menu item is active.

• If the active menu item is part of a list of predefined options

(e.g., Day of the Week) press the or + button to scroll

through the available options until the preferred option is

displayed. The option is automatically saved when the

indicator arrow is scrolled away from the value being

edited.

• If the active menu item requires you to define a value (e.g.,

a setpoint), use the or + button to decrease or increase

the value until the desired value is displayed. The selection

will be saved when the indicator arrow is scrolled up or

down.

NOTES:

1.

When setting times for the setback schedule, you

must use the or + button to change the time.

2.

The OK button, when pressed, defaults the time

setting to “--:--” (midnight).

• If the active menu item leads to a further sub-menu,

pressing the OK button displays the sub-menu options on

the LCD. Scroll through this sub-menu to position the

indicator arrow

(←) beside the desired menu item to input

or modify. Choose one of the options provided or input the

desired value for the menu item. When satisfied, scroll to

another item and your selection will be saved.

• To define or modify another item within the same menu,

scroll the up and down buttons (

^

or v) until the indicator

arrow

(←) is beside the desired option. Use the or +

buttons to set the value for that item.

• To move back (up) one level within a menu, press the

Menu button.

• To return to the Home Page display, press the Home

button.

NOTE: The AQ251 automatically returns to the Home Page

display after 60 minutes of inactivity on the keypad.

HOME PAGE DISPLAY
The Home Page is the default view displayed on the AQ251

Control Panel's LCD screen.

There are two Home Page views - Simple and Detail.

• Simple view shows 3 lines of text and is a brief description

of the system operation.

• Detail view includes the same 3 lines plus 10 lines of

additional information. Detail view is the factory default.

The choice of the Simple or Detail Home Page view is made

from the USER MENU > PREFERENCES/TIME menu option.

The Home Page display information for the Simple and Detail

views is illustrated in Fig. 2.

Fig. 2. Home Page displays (Simple and Detail).

M27749

WEDNESDAY 9:30A

PROGRAM: LEAVE RETRN SLEEP WAKE OCC UNOCC

OUTDOOR: -5

TARGET: 180 WWSD -

-

BOILER: 180

RETURN: 160

DHW: 100

ZONE COUNT: 31

WEDNESDAY 9:30A

PROGRAM: LEAVE

OUTDOOR: -5

Menu

Home

KEYPAD

HOME PAGE (SIMPLE)

HOME PAGE (DETAIL)

LCD DISPLAY