AQUATROL ZONE SYNCHRONIZING BOILER RESET CONTROLS

7

69-1979—04

When a new AQ2000 component is connected on the

AQUATROL network, its settings are communicated to the

AQ251's Boiler Control Module (AQ1520M0) within 10

seconds of being connected. If the component is an AQ1000

thermostat, the setpoints for that zone thermostat can be

modified from the Boiler Control Module as soon as it is

recognized by the Control Module.

When an AQ thermostat is disconnected from the AQUATROL

network, a message displays on the System Status page of

the AQ251 indicating “Lost Zone A-xx”, where “xx” is the

specific identity, or address, of the lost zone. This helps the

servicing contractor quickly identify the lost zone and fix its

wiring, to re-establish communication with the Control Module.

NO RETURN PROBE

n/a

No return sensor connected or it is defective.

NO SUPPLY PROBE

n/a

No supply sensor connected or it is defective.

SHORT CYCLE PROT

n/a

There is a call for heat, but less than two minutes have elapsed since the last firing of

the boiler (prevents short cycling).

VALVE INIT

n/a

Motorized mixing valve controlling the secondary loop is being initialized and

repositioned (opening or closing) to meet the secondary loop target temperature.

WATER READY

n/a

Boiler Supply Water temperature is at or above the target temperature calculated by the

AQ251.

WWSD ACTIVE

n/a

Zone calls for heat is not served because WWSD (Warm Weather Shutdown) is in

progress.

Table 2. LCD Status Notices and Error Messages. (Continued)

LCD Display

Parameter

Meaning