Dialer capture module information, Led board information, Buzzer – Honeywell 800-04433V1 User Manual

Page 10

Advertising
background image

iPGSM-COM Commercial Fire Communicator – Installation and Setup Guide

– 8 –

Dialer Capture Module Information

LED Indicator

STATUS

RED – Steady ON

Messages exist in buffer.

RED – Flashing

No messages to be sent. Waiting for messages.

GREEN – Steady ON

Normal Indication.

GREEN – Blinks every 2 sec.

PowerBoost1 communication problem.

GREEN – Blinks twice every sec.

Communication Module connection is lost.

GREEN – Blinks 10 times every sec.

PowerBoost1 and Communications Module connection is lost.

iPGSM-COM-004-V0

Dialer Capture Module

Telco 1

Telco 2

ECP

Tip 2

Ring 2

ZN-

EOL

EOL

ZN+

PWR

GND

Tip 1

Ring 1

Data Out

Data In

12V In

GND

RED

GREEN

LED Board Information

Panel Status

LED Indicator

RADIO TROUBLE

Yellow – ON when radio trouble is present.

Buzzer – Upon loss of AC power, this will
beep once every 10 seconds.

LOW BATTERY

Yellow – ON when battery is low.

Yellow – (not used)

AC LOSS

Yellow – ON when no AC is present.

AC ON

Green – ON when AC is present.






Note: Telco ports 1 (primary dialer)

and 2 (secondary dialer) may be
used instead of the terminal board.
Whichever connection method is

used, both Telco paths must be

connected to the Fire Panel.

iPGSM-COM-006-V0

Buzzer

Advertising