Igsm communications module information – Honeywell 800-04433V1 User Manual

Page 12

Advertising
background image

iPGSM-COM Commercial Fire Communicator – Installation and Setup Guide

– 10 –

iGSM Communications Module Information

TB 1

6
7
8

5

10
11

9

2
3
4

1

PRIMARY POWER: 9 - 16.5 VAC
CURRENT: 900mA PEAK, 70mA STANDBY
BATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP

FCC:XXXXXXXXXX IC: YYYYYYYYYY

RSSI

M0

M1

GPRS

IBS

iPGSM-COM-002-V0

RSSI / Mode
and
status LEDs

ON – Message transmission pending.
QUICK PERIODIC BLINK – Normal.
FAST BLINK – Message waiting for network ACK.
SLOW BLINK – Idle power abnormal.
SLOW BLINK – In unison with green LED,
registratration in progress.

Ethernet Link/Activity
GREEN

ON – Ethernet Link detected.
OFF – No link detected.
FAST BLINK – Transmitting/Receiving Data.

Link Speed
GREEN

Network Collision
YELLOW

Note: If all LEDs FAST BLINK in unison with
the RSSI LEDs this indicates a Hardware Error.

ON – No contact with network.
OFF – Normal.
SLOW BLINK – Loss of communication with the

Dialer Capture Module

(ECP fault).

ON – NOT registered with AlarmNet.
OFF – Registered with AlarmNet.
FAST BLINK – Download session with Compass
in progress.
SLOW BLINK – In unison with yellow LED,
registration in progress.

Mode
Switch

Tamper

Switch

GRN

YEL

RED

ECP OFF OFF

Zone (NOT USED) ON OFF

4204 (NOT USED) OFF ON

2 - 4204 (NOT USED) ON ON

MODULE'S RECEIVED SIGNAL STRENGTH (RSSI)

When the Mode Switch is NOT depressed, LED 1 will illuminate red.

The remaining LEDs indicate RSSI (Received Signal Strength).

MODULE'S OPERATION MODE

When the Mode Switch IS depressed, LED 1 will be OFF.
LEDs 2 and 3 indicate the module's communication mode with the Dialer Capture Module.

Mode LED 2 (yellow) LED 3 (yellow)

MODULE'S STATUS

When the Mode Switch IS depressed, LED 1 will be OFF.

LEDs 4, 5, and 6 indicate the module's Status.

FAST BLINK - Module registered, second

site available, excellent signal strength.

LED 4 (green) LED 5 (green) LED 6 (green)

ON - Connected to

Internet.

ON - Module registered, no second

site available.

ON - GPRS service

available.

OFF - No GPRS service

available

OFF - Module not registered with

network carrier.

FAST BLINK - GPRS in

use.

SLOW BLINK - Module registered, second

site available, and low signal strength.

NORMAL BLINK - Module registered, second
site available, acceptable signal strength.

OFF - Not connected

to Internet.

7720P
Programmer
Port

BLINKING – Network collision detected.
OFF – Normal.

ON – 100 MB/S link to Internet.
OFF – 10 MB/S link to Internet.

FAST BLINK – No network contact AND loss of communi-
cation with the

Dialer Capture Module

.

Advertising