Installer setup – Honeywell CHRONOTHERM T8611G User Manual

Page 5

Advertising
background image

T8611G CHRONOTHERM

®

DELUXE ZONING HEAT PUMP THERMOSTAT

5

69-1414—2

INSTALLER SETUP

The Installer Setup is used to customize the thermostat
to specific systems. Some of the options include
temperature display, changeover, and outdoor
temperature display. Installer Setup numbers are listed in
Table 4. The table includes all the configuration options
and the factory settings for the T8611.

Table 3. Default Program Settings.

A combination of key presses are required to use the
Installer Setup feature:
— To enter the installer setup, press and hold the

information i key with the increase and decrease
keys until the first number is displayed. All display
segments appear for approximately three seconds
before the number is displayed. See Fig. 9 and 10.

— To advance to the next Installer Setup, press the

Time

∆ key.

— To change a setting, use the increase or

decrease key.

— To scroll the Installer Setup numbers backward, press

the Time

∇ key.

— To exit the Installer Setup, press Run Program.

Fig. 9. Display of all LCD segments.

Fig. 10. Display of Installer Setup

number and setting.

IMPORTANT

Only configurable numbers are shown on the
device. Review Table 4 factory-settings and
mark any desired changes in the Actual Setting
column. When Installer Setup is complete,
review the settings to confirm that they match
the system.

Period

Time

Heat

Setpoint

Cool

Setpoint

Fan

Setting

Wake

6:00 AM

70°F

(21°C)

78°F

(25.5°C)

Auto

Leave

8:00AM

62°F

(16.5°C)

85°F

(29.5°C)

Auto

Return

5:00 PM

70°F

(20°C)

78°F

(25.5°C)

Auto

Sleep

10:00 PM

62°F

(16.5°C)

82°F

(28°C)

Auto

M14559

Aux Ht

Set Day/Time

Set Program

Mon
Wake Leave Return

Sleep

Outdoor

Room

Filter

Wait

System

Fan

Em Heat

On

Auto

Off

Cool

Auto

AM

PM

Hold for

Heat

Cool

Repl Batt

Recovery

DST

Tue Wed Thu Fri Sat Sun

Days

Temporary Setting

Em Ht

M14618

INSTALLER SETUP
NUMBER DISPLAY
(COLUMN 2 OF TABLE 3)

FACTORY SETTING OR OTHER
CHOICE DISPLAY (COLUMN 3
OR 5 OF TABLE 3)

Table 4. Thermostat Installer Setup Options.

Select

Installer Setup

Number (Press

Time

key to

change)

Factory Setting

Other Choices

(Press or key to change)

Actual

Setting

Display

Description

Display

Description

Not Used.

1 thru 4

Heating cycle
rate

a

5

6

Stage 2

3 or 9

3—3 cph (factory setting for
first stage of heat)

6—6 cph used for second
stage of heat

9—9 cph used for electric
heat

6 (Not Used).

7

9

Emergency heat

3 or 6

Not Used.

8 thru 11

System setting
adjustment

12

1

Manual

changeover

0 or 2

0—Auto changeover.

2—Fixed auto changeover.

Adaptive
Intelligent
Recovery™
control.

13

0

Adaptive Intelligent
Recovery™
control is activated
(system starts
early so setpoint is
reached by start of
program period).

1

Conventional recovery
(system starts recovery at
programmed time).

Advertising