T8611G CHRONOTHERM

®

DELUXE ZONING HEAT PUMP THERMOSTAT

9

69-1414—2

INSTALLER SELF-TEST

Use the Installer Self-Test to check the thermostat
operation. Refer to Table 5 for a list of the available
self-tests.

Table 5. Tests Available In Installer Self-Test.

CAUTION

Equipment Damage Hazard.
Minimum compressor off-time is bypassed
during the Installer System Test.
Avoid cycling compress quickly.

To start the system test:
Press and hold the increase and decrease keys at
the same time until 10 appears. All segments of the
display are displayed before the 10 appears.
See Fig. 10 and 11.

Fig. 11. Display of all LCD segments.

Fig. 12. Display of test number.

Refer to Table 6 for the directions and results of the
specific tests.

NOTE: Press Time

∆ to advance to the next test and

Time

∇ to go back to the previous test. Press

Run Program to exit the system test.

Test

Number

System Test Description

10-19

Heating equipment can be turned on and off.

20-29

Emergency heat equipment can be turned
on and off.

30-39

Cooling equipment can be turned on and off.

40-49

Fan equipment can be turned on and off.

60 0 to
60 19

Keyboard keys test.

70-79

Thermostat information including date code
and software versions are displayed.

M14559

Aux Ht

Set Day/Time

Set Program

Mon
Wake Leave Return

Sleep

Outdoor

Room

Filter

Wait

System

Fan

Em Heat

On

Auto

Off

Cool

Auto

AM

PM

Hold for

Heat

Cool

Repl Batt

Recovery

DST

Tue Wed Thu Fri Sat Sun

Days

Temporary Setting

Em Ht

M14612

Table 6. Installer System Test Options.

Keys to

Press

Test

Number

Description

Heating Equipment Self-Test
Time

10

Enter heating equipment self-test.

11

Stage-one heat comes on. The system fan is also energized.

12

Stage-two heat comes on. Stage-one heat and system fan remain on.

11

Stage-two heat turns off.

10

Stage-one heat and system fan turn off.

Emergency Heating Equipment Self-Test
Time

20

Change from heating to emergency heating equipment self-test.

21

Emergency heat and system fan come on.

22

Stage 2 heat comes on.

21

Stage 2 heat turns off.

20

Emergency heat and system fan turn off.

Cooling Equipment Self-Test
Time

∆ 30

Change from heating or emergency heating to cooling equipment self-test.

31

Cool and system fan come on.

30

Cool and system fan turn off.

Fan Equipment Self-Test
Time

40

Change from cooling to fan equipment self- test.