3 calculating the system current draw – Honeywell MS-9200UDLSE User Manual

Page 188

Advertising
background image

Power Supply Calculations

188

MS-9200UDLS PN 52750:E1 01/27/09

7.3 Calculating the System Current Draw

7.3.1 Overview

The control panel must be able to power all internal and external devices continuously during the
non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when
primary power is applied, use Calculation Column 1 in Table 7.3 on page 189. The control panel
must support a larger load current during a fire alarm condition. To calculate the fire alarm load on
the power supply, use Calculation Column 2 in Table 7.3 on page 189. The secondary power
source (batteries) must be able to power the system during a primary power loss. To calculate the
non-fire alarm load on the secondary power source, use Calculation Column 3 in Table 7.3 on page
189.

When calculating current draw and the battery size, note the following:

• ‘Primary’ refers to the main power source for the control panel

• ‘Secondary’ refers to the control panel’s backup batteries

• All currents are given in amperes (A). Table 7.2 shows how to convert milliamperes and

microamperes to full amperes.

7.3.2 How to Use Table 7.3 on page 189 to Calculate System Current
Draw

Use Table 7.3 on page 189 to calculate current draws as follows:

1. Enter the quantity of devices in all three columns

2. Enter the current draw where required. Refer to the Device Compatibility Document for

compatible devices and their current draw

3. Calculate the current draws for each in all columns

4. Sum the total current for each column

5. Copy the totals from Column 2 and Column 3 to Table 7.4 on page 190

Following are the types of current that can be entered into Table 7.3 on page 189:

 Calculation Column 1 - The primary supply current load that the control panel must

support during a non-fire alarm condition, with AC power applied.

 Calculation Column 2 - The primary supply current load that the control panel must

support during a fire alarm condition, with AC power applied.

 Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm

condition during a loss of AC power.

Table 7.2 Converting to Full Amperes

To convert...

Multiply

Example

Milliamperes (mA) to
amperes (A)

mA x 0.001

3 mA x 0.001 = 0.003A

Microamperes (

µ

A) to

amperes (A)

µ

A x 0.000001

300

µ

A x 0.000001 = 0.0003 A

Advertising
This manual is related to the following products: