Honeywell MS-9200UDLSE User Manual

Page 92

Advertising
background image

Programming

92

MS-9200UDLS PN 52750:E1 01/27/09

3.6.3 Zone Setup

Pressing 3 while viewing Programming Screen #2 will access the Zone Setup screens as
illustrated below:

3.6.3.1 Enable

Pressing 1 for Enable, while viewing Zone Setup Screen #1, will display the
following screen:

This screens allows the programmer to enable zones, one at a time. A flashing
cursor appears next to the Z, prompting the programmer to enter a two digit zone
number (01 - 99). When the second digit is entered, the zone will be enabled and
the cursor returns to the original position next to the Z. Another zone can then be
enabled.

PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP

Programming Screen #2

ZONE SETUP
1=ENABLE
2=DISABLE
3=ZONE 97 98 99

Zone Setup Screen #1

ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED

Zone Setup Screen #2

ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE

Zone Setup Screen #3

ZONE SETUP
1=ENABLE
2=DISABLE
3=ZONE 97 98 99

Zone Setup Screen #1

ZONE TO ENABLE
Z

Enable Screen